TOPVERT L1 Series
E-
25
Pr5-44
Rotor Resistance R1 of Motor 2
0.00065.535
0
Pr5-45
Motor 2- Electronic Thermal Relay
Selection (oL2)
0: Electronic thermal relay function
disabled
0
1: Inverter duty motor
(with independent cooling fan)
2: Standard motor
(with shaft mounted cooling fan)
Pr5-46
Motor 2- Electronic Thermal Relay
Characteristic
30600 Sec
60
Pr5-47
Heat sink Over-Heat pre–warning
setting (oH2)
0.0110.0
85.0
Pr5-48
Delay Time for Motor Selection
0.00~60.00 Sec
0.05
Pr5-49
Motor selection mode
Bit 0
(bxxxx0)
0: Cannot be switch during
operation.
b00000
1: Can be switch during
operation.
Bit 1
(bxxx0x)
0: No need to waiting for
confirm signal when
switching
1: Need to waiting for confirm
signal when switching
Group 6: Special Parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr6-00
DC Braking Current Level Amp (0~125% of drive’s rated current) A (0%)
Pr6-01
DC Braking Time during
Start-up
0.0060.00 Sec 0.00
Pr6-02
DC Braking Time during
stopping
0.0060.00 Sec 0.00
Pr6-03
Start-point for DC Braking
during stopping
0.00600.00 Hz 0.00
Pr6-04
Increasing Rate of the DC
Braking Voltage
0.01~300.00% 50.00%
Pr6-05
Momentary Power Loss
Operation Selection
0Operation stops after momentary power loss.
0
1
Operation continues after momentary power loss,
speed search Speed Search starts with Last
Output Frequency Downward
2
Operation continues after momentary power loss,
speed search starts with the Start-up frequency
Upward
Pr6-06
Maximum Allowable Power
Loss Time
0.125.0 Sec 2.0
Pr6-07
Base-Block Time for Speed
Search (BB)
0.15.0 Sec 0.5
Pr6-08
Maximum Current Level for
Speed Search
Amp (20200% of drive’s rated current) A (120%)
Pr6-09
Deceleration Time for Speed
Search
0.50120.00 Sec 3.00
Pr6-10
Auto Restart after Fault 030 times 0
Pr6-11
Speed Search during Start-up
0speed search disabled
0
1speed search through the frequency command
2FWD-speed search only
(motor only runs in FWD direction)
3REV-speed search only
(motor only runs in REV direction)
4FWD/REV speed search enabled in both
directions (FWD first)
5REV/FWD speed search enabled in both
directions (REV first)