AIR CONDITIONER (MULTI TYPE)
Owner’s Manual
For commercial use
Para utilização comercial
Para uso comercial
Outdoor Unit
Model name:
<Heat Pump Model>
MMY-MAP0804HT5P
MMY-MAP1004HT5P
MMY-MAP1204HT5P
MMY-MAP1404HT5P
MMY-MAP1604HT5P
MMY-MAP0804HT5JP
MMY-MAP1004HT5JP
MMY-MAP1204HT5JP
MMY-MAP1404HT5JP
MMY-MAP1604HT5JP
English
Español
Português
Manual del propietario 43
Owner’s manual 1
Manual do Proprietário 22
1114208801.indd cover11114208801.indd cover1 3/6/13 10:53 AM3/6/13 10:53 AM

Other manuals for Toshiba MMY-MAP1204HT5P

Questions and Answers

  • P
    Penny ButlerAug 20, 2025
    Why is my Toshiba MMY-MAP1204HT5P not cooling enough?
    • V
      vnolanAug 20, 2025
      Your Toshiba Air Conditioner might not be cooling sufficiently due to several reasons. Check if the air intake or discharge of the outdoor unit is obstructed and remove any obstructions. Ensure that all doors and windows are closed. A clogged air filter can also reduce cooling efficiency, so clean or replace it. Make sure the discharge louver of the indoor unit is set to the correct position. Also, check that the air selection and operation mode are appropriately set, and the set temperature is correct. Avoid selecting both COOL and HEAT simultaneously and verify that the outdoor temperature is within the operational range.
  • D
    Dr. Catherine Simmons MDAug 22, 2025
    What to do if my Toshiba Air Conditioner does not operate?
    • R
      Ronald StevensAug 22, 2025
      If your Toshiba Air Conditioner isn't operating, start by checking the power supply and ensuring the power switch is turned on. Inspect the power fuse or breaker and replace it if blown or reset if tripped. If the operation lamp is on, a protective device may have activated; investigate and resolve the cause. Also, check the timer settings to ensure it's not set to 'ON'. Make sure you're not trying to run COOL and HEAT simultaneously. Finally, confirm that the outdoor temperature is within the operational range.
  • R
    richardsullivanAug 25, 2025
    What to do if my Toshiba Air Conditioner displays error E23?
    • K
      Kim WoodwardAug 25, 2025
      If your Toshiba Air Conditioner shows error code E23, it indicates a communication problem between the outdoor units. First, check the number of connected outdoor units. Also, ensure that the power to all outdoor units is switched on.
  • J
    Jeremy GutierrezAug 26, 2025
    What does E06 error mean on a Toshiba MMY-MAP1204HT5P Air Conditioner and how to fix it?
    • R
      Ryan HarrisonAug 27, 2025
      If your Toshiba Air Conditioner displays error E06, it means that communication from all indoor units is interrupted after address setup, assuming normal operation is possible. Check for any disconnections in the indoor/outdoor communication line, specifically the line between the header unit and the leading indoor unit. Also, check for any communication noise that might be interfering with the signal.
  • A
    Alexander LucasAug 28, 2025
    How to fix E16 error on my Toshiba Air Conditioner?
    • H
      heather76Aug 28, 2025
      The E16 error on your Toshiba Air Conditioner means that you have exceeded the number or capacity of connected indoor units. To resolve this, adjust the number or capacity of the connected indoor units to be within the specified limits.
  • K
    kwardAug 29, 2025
    What does L08 error mean on a Toshiba Air Conditioner?
    • T
      Timothy RussellAug 30, 2025
      L08 error on your Toshiba Air Conditioner indicates an address setup error. This can occur because only the line addresses of the connected indoor units are undefined, or the outdoor line address and the line addresses of all the indoor units do not match, or the indoor addresses are duplicated (excluding units displaying E04), or a header unit is not set up in group control (except groups displaying E04). To fix this, set up the address again.
  • J
    Jacob WongAug 31, 2025
    Why does my Toshiba MMY-MAP1204HT5P Air Conditioner show error E07?
    • J
      James HarrisSep 1, 2025
      Error E07 on your Toshiba Air Conditioner can occur due to a couple of reasons. First, it may indicate that there is no outdoor terminal resistance, or there are two or more resistances (after address setup, when terminal resistance setup is changed after powering on). Check SW30 bit 2 of the header unit: if there is no connection between multiple refrigerant lines, SW30 bit 2 should be off; if there is a connection, SW30 bit 2 of the connected header unit should be turned on only for one line. Second, it could indicate a transmission circuit error at the interface side (PC board failure), in which case you should replace the interface PC board.
  • A
    Amanda MooreSep 3, 2025
    What to do if my Toshiba MMY-MAP1204HT5P displays error E04?
    • R
      Robert EdwardsSep 3, 2025
      If your Toshiba Air Conditioner displays the error code E04, it indicates that the outdoor power is off. Check that the header outdoor unit power is on.
  • B
    Bryan AndersonSep 4, 2025
    What does E08 error mean on a Toshiba MMY-MAP1204HT5P?
    • L
      Laura BeasleySep 5, 2025
      The E08 error on your Toshiba Air Conditioner signifies a duplication of indoor addresses, where the address numbers in the subcode of the check code are duplicated. The suggested solution is to set up the address again. Ensure each indoor unit has a unique address to resolve this issue. Set up the address again. Modify the setup.
  • M
    Mark StephensSep 7, 2025
    How to resolve L04 error on Toshiba MMY-MAP1204HT5P?
    • H
      Holly EvansSep 7, 2025
      The L04 error on your Toshiba Air Conditioner indicates a duplication of outdoor line addresses or a line address setup error, which may occur after connection between U1/U2 and U3/U4 connectors. To resolve this, modify the line address setup of the header unit between lines by setting up SW13 and SW14 on the interface PC board.

Summary

Comprehensive Safety and Handling

On-Unit Warning Symbols

Explains visual warning symbols and their meanings on the air conditioner unit itself.

Qualified Personnel for Installation and Repair

Details safety requirements for installation, relocation, and repair by qualified personnel.

Electrical Safety and Main Supply Disconnection

Addresses safe disconnection from the mains, installation fuse usage, and electrical safety during operation.

Remote Control Operation and Indicators

Remote Control Operation Buttons

Details the functions of each button on the remote controller for operation and settings.

Core Air Conditioner Operation

Fan Speed, Temperature, and Power Saving

Explains how to change fan speed, set desired temperature, and use power-saving mode.

Automated Timer Functions

Performance Notes and System Protection

System Protection and Failure Handling

Explains system protection mechanisms like 3-minute delay, power failure recovery, and protective devices.

Airflow Direction (Louver) Adjustment

Maintenance, Cleaning, and Energy Saving

Troubleshooting and Error Handling

Troubleshooting Symptoms and Causes

Lists common symptoms for indoor and outdoor units and their potential causes.

Error Log Confirmation and Code Interpretation

Explains how to check error logs, interpret error codes, and when to contact service.