45
FILE NO. SVM-06021
Flare at
outdoor unit side
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using vacuum pump. Do not use the
refrigerant in the outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops. (If inside oil of the vacuum pump
enters into the air conditioner which adopts R-410A, a
trouble of the refrigeration cycle may be caused.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start for evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for 20
meters) (Assuming a pump capacity of 27 liters per
minute.) Then confirm that the compound pressure
gauge reading is 101 kPa (76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves (both
sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Fig. 8-5-6
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
Do not apply excess torque, otherwise the nut
may crack depending on the conditions.
Tightening torque of flare pipe connections
The operating pressure of R-410A is higher than that
of R-22 (Approx. 1.6 times). It is therefore necessary to
tighten firmly flare pipe connecting sections (which
connect the indoor and outdoor units) up to the
specified tightening torque. Incorrect connections may
not only cause a gas leakage, but also damage the
refrigerant cycle.
Fig. 8-5-4
Fig. 8-5-5
CAUTION
KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
(1) Take away dust and moisture (Inside of the
connecting pipes).
(2) Tight connection (between pipes and unit).
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points).
Outer dia.
of copper pipe
6.35 mm
12.70 mm
Tightening torque
16 to 18 (1.6 to 1.8 kgf·m)
50 to 62 (5.0 to 6.2 kgf·m)
(Unit : N·m)
Use a wrench to secure.
Flare nut
Half union
Use a torque wrench to tighten.
Externally
threaded side
Internally
threaded side
Pressure gauge
Manifold valve
101 kPa (76 cmHg)
Handle Lo
Connecting pipe
Compound pressure gauge
Vacuum
pump
Handle Hi
(Keep full closed)
Charge hose (For R410A only)
Charge hose (For R410A only)
Vacuum pump adapter
for counter-flow
prevention
(For R410A only)
Service port (Valve core (Setting pin))
Packed valve
at liquid side
Packed valve at gas side