【F1.06】 Frequency Command Selection (operation panel)
The settings are listed as below:
0: The frequency command cannot be changed in the monitor mode to avoid the
fault occurred by changing the frequency in the monitor mode.
1: The frequency command can be changed in the monitor mode.
【F1.07】 Frequency Command Auto-Storing (operation panel)
The settings are listed as below:
0: The frequency command setting does not auto-store in the monitor mode.
1: The frequency command setting is auto-stored after 3 minutes in the monitor
mode.
【F1.08】 Main Display Selection
a. The settings are listed as below:
1: Output frequency
2: Frequency command
3: Output voltage
4: DC bus voltage
5: Output current
6: Terminal status
7: Temperature of heat sink
8: Display mode 8 (F1.11)
b. Above display modes can be selected as the primary display and other display
modes becomes secondary display modes.
c. When the drive is idle without any operation for 3 minutes, the secondary display
will be automatically changed to the primary display mode.
【F1.11】 Display Mode 8
The settings are listed as below:
0: Terminal status
1: Temperature of heat sink
2: Motor rotation speed(RPM)
3: Machine speed(MPM)
4: The sector of sequential operation control
5: The cycle of sequential operation control
6: Counting value
7: Current limit level
8: Primary frequency command
9: Secondary frequency command
10: PID command
11: PID feedback
【F1.13】 Machine Speed Ratio
The machine speed display in the monitor mode
Machine speed = Machine speed ratio (F1.13) × Output frequency
44