2.0 INSTALLATION
12
Generator Output Balancing Autotransformer
Single 120 Volt AC Load
This configuration allows the 120/240 volt AC generator output to be
equally divided (balanced) between its L1 and L2 outputs. In this example, the
generator is using both its L1 and L2 outputs to supply a high current 120 volt
AC load. Balancing the generator in this way improves generator performance
and life, plus results in higher battery charge rates.
Procedure
Connect the L1 output of the generator to the lower breaker (point A).
Connect the L2 output of the generator to the upper breaker (point C).
Connect the ground wire from the generator to the T240 GROUND block.
Connect the neutral wire from the generator to the T240 NEUTRAL block.
Connect the inverters 120 volt AC input to the service crimp on the lower
breaker (point B).
Connect a ground wire from the inverter to the GROUND block in the
T240.
Connect a neutral wire from the inverter to the NEUTRAL block in the
T240 .
Follow the instructions for wiring the inverter to the loads as specified in
the inverters operation manual.