Service Facts
© 2013 Trane
NOTICE: The manufacturer has a policy of continuous product and product data improvement, and it
reserves the right to change design and specifications without notice.
IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is to
remain with this unit. Please return to service information pack upon completion of work.
WARNING:
HAZARDOUS VOLTAGE-
DISCONNECT POWER and DISCHARGE
CAPACITORS BEFORE SERVICING
SINGLE PACKAGED
GAS HEATING / ELECTRIC COOLING
4YCY4036B1075/1096B
PRODUCT SPECIFICATIONS
4YCY4036B-SF-1H
1 Certified in accordance with the Unitary
Air-Conditioner Equipment certification
program, which is based on AHRI
Standard 210/240. Sound Power val-
ues are not adjusted for AHRI 270-95
tonal corrections.
2 All models are certified to UL 1995.
Ratings shown are for elevations up to
2000 ft. For higher elevations reduce
ratings at a rate of 4% per 1000 ft.
elevation.
3 Convertible to LPG.
4 This value is approximate. For more
precise value, see Unit Nameplate.
5 Based on U.S. Government Standard
Tests.
6 Filters must be installed in return air
stream. Square footages listed are
based on 300 f.p.m. face velocity. If
permanent filters are used size per
manufacturer's recommendation with
a clean resistance of 0.05" W.C.
7 Standard Air - Dry Coil - Outdoor.
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUH
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)
Sound Power Rating [dB(A)]
Performance Heating
Input BTUH - 1st Stage (Natural Gas)
Input BTUH - 2nd Stage (Natural Gas)
AFUE
Temp. Rise — Min/Max (°F)
Orifice Qty / Drill Size (Natural Gas)
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacity
Fuse Size — Max. (amps)
Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz
R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
INDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Refrigerant Control
Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g. 7
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M.
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)
REFRIGERANT
Charge (lbs.)
GAS PIPE SIZE (in.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
4YCY4036B1075B
208-230/1/60
38000
1210
3.166
12.0 / 14.2
69
56250
75000
79.5
30 / 60
2 / #33
208-230/1/60
26.2
40
40
SCROLL
208-230/1/60
16.7 / 79
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
3320
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4
R410A
7.80
1/2
H X W X L
47.86 / 44.5 / 52.03
488 / 392
4YCY4036B1096B
208-230/1/60
38000
1210
3.166
12.0 / 14.2
69
72000
96000
80.0
40 / 70
3 / #37
208-230/1/60
26.2
40
40
SCROLL
208-230/1/60
16.7 / 79
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
3320
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4
R410A
7.80
1/2
H X W X L
47.86 / 44.5 / 52.03
493 / 397
Question and Answer IconNeed help?

Do you have a question about the Trane 4YCY4036B1096B and is the answer not in the manual?

Trane 4YCY4036B1096B Specifications

General IconGeneral
BrandTrane
Model4YCY4036B1096B
CategoryCooling boxes
LanguageEnglish

Summary

Safety Warnings and Precautions

General Safety Hazards

Warns of hazards from high voltage, moving fans, and combustible gas during service.

Chemical and Gas Hazards

Addresses California Prop 65 warning and propane gas explosion hazards.

Electrical Safety and Wiring

Hazardous Voltage Warning

Emphasizes disconnecting power before servicing due to hazardous voltage.

Sequence of Operation

Heating Cycle Operation

Details the sequence for 1-stage and 2-stage heating calls and satisfaction.

Safety Sequence Operations

Explains operation of safety devices like TCO, RO, PS, and ignition trials.

Refrigerant Charging Procedure

Subcooling Charging Method

Outlines the subcooling method for charging R-410A systems in cooling.

Troubleshooting Common System Faults

Refrigerant Circuit Troubleshooting

Identifies primary and secondary causes for refrigerant circuit issues like pressure problems.

Electrical System Troubleshooting

Lists causes for electrical faults such as compressor or fan start failures.

IGN Diagnostic Indicators

Related product manuals