Electrical Schematics
54 CG-SVX038A-EN
Figure 22. Instructions — CAUJ condenser control circuit modification:
fan cycling control by CCAR compressor chillers
A
Instructions
Circle
Remove wire 65C and/or the jumper installed. Connect 1TB3-6 to TBD 3 at Trane Chiller.
Remove wire 64E. Connect 1TB3-5 to TBD 2 at Trane Chiller. This is the first fan on and last fan off.
NOTES:
2
3
1
Remove wire 63A. Connect 1TB3-4 to TBD 4 at Trane Chiller. This is the last fan on and
Ambient t-stat will not be used. This is the second fan on and second fan off.
D
B
2
4
Remove wire 63A. Connect 1TB3-4 to TBA 18 at Trane Chiller. This is the last fan on and
Circle
Instructions
1
Step
Remove wire 64E. Connect 1TB3-5 to TBA 16 at Trane Chiller. This is the first fan on and last fan off.
Reference
Ambient t-stat will not be used. This is the second fan on and second fan off.
C
COMPLETE
Reference
Connect 1TB2-1 to TBA 15 at Trane Chiller.
Remove wire 65C and/or the jumper installed. Connect 1TB3-6 to TBA 17 at Trane Chiller.
first fan off. The installed pressure switch will not be used.
3
Step
1
1
3
B
Connect 1TB2-1 to TBA 15 at Trane Chiller.
D
2
first fan off. The installed pressure switch will not be used.
Circle
Remove wire 64E. Connect 1TB3-5 to TBA 16 at Trane Chiller. This is the first fan on and last fan off.
A
FOR CONTROL OF 3 FAN CONDENSER:
FOR CONTROL OF 2 FAN CONDENSER:
E
Connect 1TB2-1 to TBD 1 at Trane Chiller.
5
B
Instructions
C
Step
Initial/Date
Initial/Date
B
from the CCAR Compressor Chiller to the CAUJ condenser.
Initial/Date
FOR CONTROL OF 4 FAN CONDENSER:
COMPLETE
A
E
Connect 1TB2-1 to TBD 1 at Trane Chiller.
D
5
3
Remove wire 77E. Connect 1TB3-10 to TBD 6 at Trane Chiller.This is the first fan on and last fan off.
CCAR units are designed for operation down to a minimum of 40°F ambient.
first fan off. The installed pressure switch will not be used.
A
Instructions
Reference
The installed pressure switch will not be used.
Remove wire 64E. Connect 1TB3-5 to TBD 2 at Trane Chiller. This is the first fan on and last fan off.
COMPLETE
Circle
Remove wire 76A. Connect 1TB3-9 to TBD 7 at Trane Chiller. This is the last fan on and first fan off.
first fan off. The installed pressure switch will not be used.
Step
Remove wire 63A. Connect 1TB3-4 to TBA 17 at Trane Chiller. This is the second fan on and
Remove wire 63A. Connect 1TB3-4 to TBD 3 at Trane Chiller. This is the last fan on and
4
2
COMPLETE
Ambient t-stat will not be used. This is the second fan on and second fan off.
Remove wire 77E. Connect 1TB3-10 to TBD 6 at Trane Chiller. This is the first fan on and last fan off.
G7
Initial/Date
FOR CONTROL OF 6 FAN CONDENSER:
Remove wire 78C and/or the jumper installed. Connect 1TB3-11 to TBD 7 at Trane Chiller.
The installed pressure switch will not be used.
F6
Remove wire 76A. Connect 1TB3-9 to TBD 8 at Trane Chiller. This is the last fan on and first fan off.
G
D
All CCAR/CAUJ applications require that the CCAR Compressor Chiller control the condenser fan cycling.
For Fan Cycling Control - One control wire for each condenser fan plus a common must be run
Reference
4
CAUJ Condenser Control
Wiring Modification:
Fan Cycling Control by CCAR
Compressor Chillers
Trane CAUJ Condenser Control Wiring Modification
Fan Cycling Control by Trane CCAR Compressor Chillers
A
THREE PLACE DECIMAL
JOB #:
09/19/13
09/19/13
TRANE. ANY REPRODUCTION IN PART
R80500015B
LAH
09/19/13
DRAWING IS THE SOLE PROPERTY OF
BAR
EGN
SCALE:1:1
DWG. NO.
09/19/13
REV.
OR AS A WHOLE WITHOUT THE WRITTEN
75606-3066
PERMISSION OF TRANE IS PROHIBITED.
COMMENTS:
SHEET 1 OF 1
Q.A.
MFG APPR.
ENG APPR.
CHECKED
DRAWN
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DO NOT SCALE DRAWING
SIZE
SMH
NAME
MATERIAL
DATE
FINISH
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
ANGULAR: MACH BEND
TWO PLACE DECIMAL
LONGVIEW, TX
P.O. BOX 3066

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Cold Generator CGWR Series and is the answer not in the manual?

Trane Cold Generator CGWR Series Specifications

General IconGeneral
BrandTrane
ModelCold Generator CGWR Series
CategoryChiller
LanguageEnglish

Related product manuals