EasyManua.ls Logo

Trane Horizon OAND540A - Page 49

Trane Horizon OAND540A
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Performance Data
OAU-SVX01H-EN 49
Table 12. OAKE general data—cooling 12–20 tons high efficiency
12 Tons Downflow 15 Tons Downflow 17 Tons Downflow 20 Tons Downflow
OAKE144A OAKE180A OAKE210A OAKE240A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 160,024 (46.90) 189,076 (55.41) 225,948 (66.22) 258,766 (75.84)
Heating Performance
Gross Heating Capacity, Btu (kW) 143,650 (42.10) 185,800 (54.45) 208,973 (61.24) 244,186 (71.56)
CFM
Nominal cfm/AHRI rated cfm (m
3
/h) 1500–3000 (883–1766)
1875–3750 (1104–
2207)
2125–4250 (1251–
2501)
2500–5000 (1471–
2943)
Compressor
Number 2222
Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance
Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 1/2 (12.7) 1/2 (12.7)
Face Area, ft
2
(m
2
) 30 (2.79) 30 (2.79) 31 (2.88) 31 (2.88)
Rows 2222
FPI 12121212
Indoor Coil
Type High Performance High Performance High Performance High Performance
Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
Face Area, ft
2
(m
2
) 9 (0.84) 10 (0.93) 16 (1.49) 16 (1.49)
Rows 4444
FPI 12121212
Refrigerant Control TXV TXV TXV TXV
Drain Connection Size, in. (mm) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4)
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used 2 3 3 3
Diameter, in. (mm) 24 (609.6) 24 (609.6) 24 (609.6) 24 (609.6)
Drive Type Direct Drive Direct Drive Direct Drive Direct Drive
No. Speeds 1111
CFM (m
3
/h) 19,500 (11,477) 19,500 (11,477) 19,500 (11,477) 19,500 (11,477)
Number Motors 3333
Motor HP (kW), per motor 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) 1.0 (0.75)
Motor RPM 1,140 1,140 1,140 1,140
Indoor Fan
Type Backward Inclined Backward Inclined Backward Inclined Backward Inclined
Number Used 1 1 1 1
Diameter Varies Varies Varies Varies
Drive Type Direct Drive Direct Drive Direct Drive Direct Drive
Number Motors 1111
Motor HP (kW), Standard–Oversized 1–5.0 (0.75–3.73) 1–5.0 (0.75–3.76) 1–7.5 (0.75–5.59) 1–7.5 (0.75–5.59)
Motor RPM, Standard–Oversized 1750–3500 1750–3500 1750–3500 1750–3500
Motor Frame Size, Standard–Oversized Varies Varies Varies Varies
Filters
Type Furnished Refer to “OAU Filter
Guide” in “Appendix,”
p. 68
Refer to “OAU Filter
Guide” in “Appendix,
p. 68
Refer to “OAU Filter
Guide” in “Appendix,”
p. 68
Refer to “OAU Filter
Guide” in “Appendix,”
p. 68
Number Size Recommended
Refrigerant Charge, lb of R-410A
Downflow See Nameplate See Nameplate See Nameplate See Nameplate

Table of Contents