Installation—Sensors
UV-SVN02C-EN 39
Wireless Sensor Specifications
The following table presents specifications for all models
of the wireless sensor sets.
Sensor operating temperature 32°F to 122°F
Receiver operating temperature -40°F to 158°F
Storage temperature -40°F to 185°F
Storage and operating humidity
range
5% to 95%, non-condensing
Accuracy 0.5°F over a range of 55ºF to 85°F
Resolution 0.125°F over a range of 60°F to 80°F
0.25°F when outside this range
Setpoint functional range (WDS
only)
50°F to 89.6°F
Receiver voltage 24 V nominal ac/dc ±10%
Receiver power consumption <1 VA
Housing Polycarbonate/ABS blend, UV
protected, UL 94-5VA flammability
rating, suitable for application in a
plenum
Mounting 3.24 in (8.26 cm) for 2 mounting
screws (supplied)
Sensor battery (2) AA, 1.5 V, 2800 mAh, lithium,
5-year life, UL listed
Range
(a)
(a) Range values are estimated transmission distances for satisfactory op-
eration. Actual distance is job specific and must be determined during
site evaluation.
Open range: 2,500 ft (762 m)
(packet error rate = 2%)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
Output power 100 mW
Radio frequency 2.4 GHz (IEEE Std 802.15.4-2003
compliant)
(2405 to 2480 MHz, 5 MHz spacing)
Radio channels 16
Address range 000 to 999
Minimum time between
transmissions
30 seconds
Maximum time between
transmissions
15 minutes
UV-SVN02_-EN.book Page 39 Thursday, January 24, 2013 4:48 PM