Installation Instructions
P & Q 600 SERIES DUAL COIL
3 WIRE DC SOLENOIDS
MOUNTING SOLENOID AND ELECTRICAL CONNECTIONS
1. Securely bolt the solenoid in its mounting position, making sure to align the plunger as straight as possible
to the connecting linkage. Do Not Connect the linkage to the lever at this time.
2. Using the “Wire Gage Recommendation Table below, select the proper wire size for your installation.
Wire the solenoid for your installation as shown on page 2 of these instructions.
IMPORTANT
To insure proper solenoid operation, the total connecting wire length for both leads combined, must not exceed the
recommended maximum lengths indicated in the Wire Size Recommendation Table below:
Solenoid Lead Identification:
WHITE PULL COIL / HIGH CURRENT
RED HOLD COIL / LOW CURRENT
BLACK GROUND
CAU TION!
Coils that burn out due to improper electrical connections are not
covered by factory warranty. If you have any questions concerning
proper installation, contact the factory before proceeding.
1
1601006440251610--------
24 VDC
40251610642.5--------
12 VDCP & Q
612 613
2401509660382415--------
24 VDC
603824159.564----------
12 VDCP & Q 610
6GA8GA10GA12GA14GA16GA18GA20GA22GA
Maximum lead length or all leads (in feet)
Wire Gage/Size
Rated
Voltage
Solenoid
WIRE SIZE RECOMMENDATION TABLE
SYSTEM # 1 - ON-TO-RUN , FUEL SHUTDOWN
APPLICATIONS
Solenoid is wired into existing starting system of the engine.
No added “high current” relays are required since the solenoid
“pull coil” (high current) power comes directly from the engine
starter. Wire the solenoid as shown in the schematic below:
Note: If wired as shown to the right, and
solenoid is improperly adjusted, solenoid
plunger will release when operation is
shifted to the “holding mode” after the
engine starts. If the plunger releases, no
damage will occur to the solenoid. Only
readjustment of the linkage is required.
Question and Answer IconNeed help?

Do you have a question about the trombetta P & Q 610 and is the answer not in the manual?

trombetta P & Q 610 Specifications

General IconGeneral
Brandtrombetta
ModelP & Q 610
CategoryPower Inductor
LanguageEnglish

Summary

Mounting Solenoid and Electrical Connections

Wire Gage Recommendation Table

Table listing recommended wire sizes based on total lead length and solenoid type.

Solenoid Lead Identification

Identifies the color coding for solenoid pull coil, hold coil, and ground leads.

Electrical Connection Caution

Warning about coils burning out due to improper electrical connections and warranty implications.

System 1: On-To-Run Fuel Shutdown

Wiring Diagram for System 1

Schematic showing solenoid wiring for 'On-To-Run' fuel shutdown applications using the existing starting system.

System 2: Engine Speed/RPM Control Applications

Wiring Diagrams for S500-A5/A6 Modules

Wiring configurations for S500-A5 and S500-A6 modules, including 12V and 24V direct and remote operation.

Wiring Diagrams for S500-A50/A60 Modules

Wiring configurations for S500-A50 and S500-A60 modules, with notes on module usage and solenoid connections.

Module Installation Procedures

Steps for energizing solenoid coils, connecting linkage, adjusting, and checking linkage movement with modules.