NEWTECH PRO
1-2-3 KVA ONLINE
UNINTERRUPTIBLE POWER SUPPLY
USER MANUAL

Questions and Answers

  • K
    kariramseyJul 30, 2025
    What to do if the icon is flashing on the LCD display and alarm is sounding twice every second on my Tuncmatik NEWTECH PRO 1 KVA?
    • C
      Cynthia JoyceJul 31, 2025
      If the icon is flashing on the LCD display and the alarm is sounding twice every second on your Tuncmatik UPS, it indicates an overload. This can happen if the UPS is overloaded, or if devices connected to the UPS are being fed directly by the electrical network via the Bypass. It can also happen if the UPS is locked in Bypass mode after repetitive overloads. To resolve this, remove excess loads from the UPS output. If the UPS is locked in Bypass mode, remove excess loads, then shut down the UPS and restart it.
  • A
    Amy KleinAug 5, 2025
    Why is the battery backup time shorter than nominal value on my Tuncmatik NEWTECH PRO 1 KVA UPS?
    • C
      Cynthia ZavalaAug 5, 2025
      If the battery backup time on your Tuncmatik UPS is shorter than expected, it could be due to the batteries not being fully charged or the batteries being defective. First, charge the batteries for at least 5 hours and then check the capacity. If the problem continues, it may be necessary to contact your dealer to replace the battery.
  • B
    Brittany BennettAug 9, 2025
    What to do if there is no indication and alarm even though the mains is normal on my Tuncmatik NEWTECH PRO 1 KVA UPS?
    • J
      Jennifer OlsonAug 10, 2025
      If your Tuncmatik UPS shows no indication and alarm even when the mains is normal, it could be due to a couple of reasons. First, check if the AC input power cord is firmly connected to the mains. Second, make sure the AC input is correctly plugged into the AC input, not the UPS output.
  • B
    brittney23Aug 14, 2025
    Why is the icon and the warning code flashing on LCD display and alarm is sounding every second on my Tuncmatik UPS?
    • J
      Joshua TrujilloAug 15, 2025
      If the icon and warning code are flashing on the LCD display and the alarm is sounding every second on your Tuncmatik UPS, it could be due to several reasons: * The EPO function might be activated. If so, set the circuit in a closed position to disable the EPO function. * The line and neutral conductors of the UPS input might be reversed. Rotate the mains power socket by 180° and then connect it to the UPS system. * The external or internal battery might be incorrectly connected. Check if all batteries are connected well.
  • S
    Scott MccormickAug 20, 2025
    What to do if fault code 43 is shown and the icon is lighting on LCD display and alarm is continuously sounding on my Tuncmatik NEWTECH PRO 1 KVA UPS?
    • T
      Tom GentryAug 20, 2025
      If fault code 43 is shown, the icon is lighting on the LCD display, and the alarm is continuously sounding on your Tuncmatik UPS, it means the UPS shut down automatically due to an overload at the UPS output. To fix this, remove excess loads from the UPS output and restart it.
  • M
    Mallory PerezAug 25, 2025
    What to do if fault code 14 is shown and the icon is lighting on LCD display and alarm is continuously sounding on my Tuncmatik UPS?
    • M
      Melissa TaylorAug 25, 2025
      If fault code 14 is shown, the icon is lighting on the LCD display, and the alarm is continuously sounding on your Tuncmatik UPS, it indicates that the UPS shut down automatically because a short circuit occurred on the UPS output. Check the output wiring and if connected devices are in a short circuit status.

Summary

Important Safety Warning

1-1. Transportation

Transport the UPS in its original packaging to prevent shock and impact.

1-2. Preparation

Allow the UPS to acclimate to the environment for at least two hours before installation.

1-3. Installation

Avoid connecting devices that overload the UPS, like laser printers, to output sockets.

1-4. Operation

Do not disconnect the mains cable during operation to maintain protective earthing.

1-5. Maintenance, Service and Faults

Repairs should only be performed by qualified personnel due to hazardous voltages.

Installation and Setup

2-1. Rear Panel View

Details the rear panel ports and connectors for different NEWTECH PRO UPS models.

2-2. Setup the UPS

Guides through UPS input/output connections, network, EPO, power-on, software installation, and external battery connection.

Operations

3-1. Button Operation

Details the functions of the ON/Mute and OFF/Enter buttons for UPS control.

3-2. LCD Panel

Explains the LCD panel indicators for backup time, faults, load, and operating modes.

3-3. Audible Alarm

Details audible alarms for UPS conditions like low battery, overload, and faults.

3-4. LCD Display Wordings Index

Index of abbreviations and meanings displayed on the UPS LCD screen.

3-5. UPS Setting

Explains UPS parameter settings for output voltage, frequency, ECO, and bypass.

3-6. Operating Mode Description

Describes UPS operating modes including Online, ECO, Converter, Battery, Bypass, and Standby.

3-7. Faults Reference Code

Lists fault events, codes, and icons for troubleshooting UPS issues.

3-8. Warning Indicator

Details UPS warning indicators, icons, flashing patterns, and alarms.

Troubleshooting

Storage and Maintenance

5-1. Operation

Discusses UPS operation, battery replacement, and spent battery disposal.

Storage

Guidelines for storing the UPS, including charging requirements and environmental conditions.

Tuncmatik NEWTECH PRO 1 KVA Specifications

General IconGeneral
Capacity1 KVA
Output Frequency50/60 Hz
TopologyLine Interactive
Input Voltage220/230/240 VAC
Output Voltage220/230/240 VAC
Battery TypeSealed Lead Acid