l Primary: Compatible listed control unit's land line to central station (primary).
l Secondary: LE4010 transmission through wireless network to central station.
Every 24 hours, a check-in signal must be sent to the central station over the primary dialer. The LE4010 sends
a heartbeat test transmission to the supervising station every 24 hours. Each communication path shall be mon-
itored for integrity (DACT shall have line monitoring enabled and LE4010 shall have cellular connection
supervision enabled).
Power for model LE4010 shall be provided by one of the two compatible power supplies:
a. Mircom Model DTC-300A(W)(R), digital alarm communicator transmitter
b. Simplex control panel 4100U with converter module 4100-5152 installed
Note: Wiring between the LE4010 and FACP/Power Supply shall be made in the same room, in metal conduit
and not longer than 20ft.
3G4010/LE4010 Installation Manual