SPECIFICATIONS
Physical
Enclosure Dimensions (H x W x D) . . 356 x 305 x 89 mm
(14 x 12 x 3.5 in)
RM-4E Board-Only
Dimensions (H x W) ............. 136 x 181 mm
(5.375 x 7.125 in)
Weight (with 4Ah battery) .........5.9 kg (11 lbs)
Weight (without battery) ..........4.5 kg (8 lbs)
Construction ................... 20 AWG metal wall mounted locking
cabinet with tamper switch on door
Environmental
Operating and Storage
Temperature ................... 0 ° to 50°C (32° to 122°F)
5 to 95% RH, non-condensing
Electrical
Power Requirements
without Reader or Relays ......... +12 VDC +/- 5% or +24 VDC +/-10%,
280 mA max
Power Requirements, Maximum,
with Reader and Relays .......... +12 VDC +/- 5% or +24 VDC +/-10%,
550 mA max
Output Relay Power Ratings .......Up to 30 VAC/DC, 5A maximum
Reader LED Output Controls ......4.0 volts to 5.25 volts, 20mA max
Power Available for Reader ........ 5 VDC +/- 10% or 12 VDC +/- 10%,
125mA max (at 5V or 12V)
Optional Battery ................ 12V/4Ah battery provides
nominal 4 hours backup time
Regulatory
UL 294
CE, including EN50081-1, EN50130-4, EN50133
FCC Part 15 Class A
RoHS
Communications
Communications Bus ............ RM bus from iSTAR controller
or apC/8X panel
Communications Type ...........RS-485 half duplex, two-wire
Maximum Distance ..............1,219 m (4,000 ft)
Reader, Inputs & Outputs
Reader Ports ..................One
Reader Support ................Wiegand or magnetic stripe
Reader Control Lines Available .....Red LED, green LED, yellow LED, beeper
Keypad Support ................ Terminals provided for external 3x4
matrix keypad
Supervised Inputs ...............Two, double-resistor
Output Relays ..................Two, Form C, dry contact
Tamper Input ..................One
Indicators and Switches
Three status LEDs for each supervised input
LED on each relay output
LEDs for RS-485 transmit and receive
LED for power-on
Optional LCD for diagnostics
Eight position dipswitch for feature selection:
• Wiegand/magnetic stripe reader type
• Tamper bypass
• LED pattern
• RM bus termination
• Input LED disable
Mounting Specifications
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Availability varies by region;
contact your sales representative. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.
©2008 Tyco International Ltd. and its respective companies. All rights reserved. SH0118-DS-200810-R02-A4-EN
www.swhouse.com
30.48 cm
(12.00 in)
26.67 cm
(10.50 in)
3.81 cm
(1.50 in)
3.175 cm
(1.25 in)
33.02 cm
(13.00 in)
35.56 cm
(14.00 in)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Software House RM-DCM-2 and is the answer not in the manual?

Tyco Software House RM-DCM-2 Specifications

General IconGeneral
BrandTyco
ModelSoftware House RM-DCM-2
CategoryControl Systems
LanguageEnglish