13
18
PRESSURE
Eect: Stop burner, Pump on at
maximum speed.
RESET: AUTO
Check circulation, check
installation
19
FLOW
OVERTEMPERATURE.
It is activated when the flow
temperature is > 95. Resetting is
automatically carried out when the
temperature is < 80.
Eect: Stop burner, Pump on at
maximum speed.
Circulation control
14
RETURN SENSOR
Auxiliary (SRG) sensor interrupted
Check the wiring, if needed, replace the auxiliary sensor
40
MINIMUM WATER FLOW (DK)
The main water ow is not
detected by DK within 20’’ after
activating the pump.
It is enabled if the parameter
FS = 1, 2 or 3 ..
If FS.1 = 0,
Eect: Stop burner
RESET: AUTO
Check circulation, check
installation
73
WATER DEFICIENCY PRES-
SURE SWITCH
The fault is only checked if param-
eter FS 2 = 1.
It is detected if input DK is active
for more than 20” after disabling
the pump.
Eect: Stop burner
RESET: AUTO
Check circulation, check
installation
08
WATER DEFICIENCY
Insufficient water pressure and
consequent intervention of the
minimum water pressure - pres-
sure switch (DK).
Eect: Stop burner
RESET: AUTO
17
HEAT EXCHANGER
FREEZING
Heat exchanger freezing is detect-
ed. If the heating sensor detects
a temperature below 2° C, burner
ignition is inhibited until the sensor
detects a temperature above 5°C.
Eect: Stop burner Pump active
for 5' at maximum speed to obtain
heat from the system.
RESET: AUTO
58
FLOW SENSOR
SGM
Burner OFF.
RESET: AUTO
It is detected only if more than 1 BMM is connected
(cascade application)