8
896 TU Unit temperature °C / °F
0 ÷ 1 0
309 St Application Code
0 Burners cascade (BMM) 0
1 Individual burners (only 1 BMM connected) 1
368 VA1 Programmable Relay #1
0 Main pump control 0
1 Boiler status
369 VA2 Programmable Relay #2
0 activated only if the fault prevents
inputting the requested number
burner correctly.
0
1 Activated by any boiler failure
771 PS Water Pressure Sensor
0 Not enabled 0
1 Enabled
768 LG Sens. Min Gas Pressure
0 Not enabled 0
1 Enabled
793 COC Chimney Obstruction Sensor
0 Not enabled 0
1 CO
2 CO and COL
622 FS Minimum Flow Sensor
0÷7 Bit map 0
1 Enabled Flow Sensor / Global Fault
3 Enabled Flow Sensor / Local Fault
5 Enabled Flow Sensor / Global Fault
and check Flow Switch fault
7 Enabled Flow Sensor / Local Fault
and check Flow Switch fault
Software Code (read only)
Software Revision (read only)
Code
Sym-
bol
Value Description Default
settings
BCM user
settings