7
650 dL °C DHW: Minimum Set-point
250 ÷ 450 350
385 dH °C DHW: Maximum Set-point
500 ÷ 650 650
360 dt Heater Adjustment
0 ÷ 15 0 = 85° - 1 ÷ 15 = 0
656 drt °K
-20 ÷ 20 4
657 drH °K DHW: Requested Temp. Hysteresis
1 ÷ 20 8
310 dpT sec. DHW Pump: Post-circulation
5 ÷ 600 60
660 dbT °C DHW: Temp. Maximum Boiler
50 ÷ 85 75
48 ChSet °C CH#1: Set-point
20 ÷ 85 85
64 ChPO CH#1: Parallel Supply
0 ÷ 1 0
346 mC %
o Burner modulation minimum %
0 ÷ 1000 (*) minimum modulation that determines the
burner's switching o, only with cascade
management
(*)
250
600 mB Burners: Min. Inserted
1 ÷ 8 1
616 BSt sec. Gen: Insertion Time
30 ÷ 900 120
613 BRt sec. Gen: Removal Time
30 ÷ 900 120
336 HS °C/min Temperature Gradient
1 ÷ 30 5
353 HP °K CH PID: Proportional
0 ÷ 50 25
354 HI °K CH PID: Integrative
0 ÷ 50 12
478 Hd °K CH PID: Derivative
0 ÷ 50 0
816 MI Modbus Address
0 ÷ 127 1
817 MT sec. Modbus Time-out
0 ÷ 240 30
Code
Sym-
bol
Value Description Default
settings
BCM user
settings