Unical MODULEX EXT 150 - Mixing Header; Mixing Header Filter

Unical MODULEX EXT 150
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Instructions for the installer
3.10 - MIXING HEADER
n order to ensure correct boiler operation it is necessary to use
a mixing header which guarantees:
- the separation and collection of circuit dirt
- optimal air venting
- hydraulic de-coupling of the two hydraulic circulation
circuits
- balancing of the circuits
mod. Ø
EXT 100-150 DN 50
EXT 200-250 DN 50
EXT 300-350 DN 50
Recomended installation
Mixing HeaderModulex Ext 100 - 350
cod.00361976
M=DN100-(G4’’)
R=DN100-(G4’’)
3.11 - MIXING HEADER FILTER
UNICAL suggests the installation of a Y lter
on the return pipe so that it can be cleaned if
necessary.
This lter will protect the boiler from the heating
system dirt.
Boiler
Circuit
Heating
System
Circuit