47
Instructions for the installer
INJECTORS – PRESSURES
SWEEPER MODE
The function is active for a time
of 15 min, after that the planned
parameters are restored.
MODULEX EXT: 100 - 150 - 200 - 250 - 300 - 350
GasType Supply
pressure
Ø
Injectors
Diaphragm
Fan Speed
CO
2
levels
Starting
power
[mbar] (mm) [mm] min max [%] [%]
FL
[% FU]
FU [Hz] min max IG
Gasnat.(G20) 20 7 - 31 98 9,1 9,1 80
Gasnat.(G25) 25 9 - 31 98 9,1 9,1 80
Propan(G31) 37 7 - 30 91 10,8 10,8 80