6: Troubleshooting
6-2 UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
6.2.2 Fault identification and rectification messages and alarms
The major alarm conditions that will be encountered are:
6.3 Contacting Service
Uninterruptible Power Supplies Limited has a service department dedicated to providing routine maintenance
and emergency service cover for your UPS. If you have any queries regarding your UPS please contact us.
We recommend that your UPS is protected by an Extended Warranty Agreement (see Section 2 for details).
These agreements assist us in caring for your UPS correctly, ensuring that it is well maintained and attended
to promptly should any problems occur.
Alarm Condition Meaning Suggested Solution
UPS FAULT There is a fault within the UPS and
therefore normal operation cannot be
guaranteed.
Call the authorised service centre for
assistance.
MAINS BYP/RECT FAULT Mains power supply is outside
prescribed tolerance.
The input power to UPS is too low, too
high, or missing.
If site power appears to be OK, check the
input circuit breakers etc. supplying the
UPS.
OUTPUT SHORT There is a short circuit at the output of
UPS (on load side).
Check all output connections and repair as
required.
OVERLOAD Load exceeds the UPS rated power. Identify which piece of equipment is
causing the overload and remove it from
the UPS.
Do not connect laser printers,
photocopiers, electric heaters, kettles etc.
to the UPS.
OVERTEMPERATURE UPS temperature has exceeded the
allowed value.
Check the ambient temperature of the UPS
is less than 30° C.
If the ambient temperature is normal call
the authorised service centre for
assistance.
BATTERY CHARGER OFF The attached battery and the battery
charger set-up do not correspond or
battery charger fault.
Call the authorised service centre for
assistance.
INVERTER FAULT Inverter is faulty. Call the authorised service centre for
assistance.
SYNCHRON FAULT The inverter and mains are not
synchronised.
The frequency of the UPS input voltage is
outside operational limits and the UPS
static bypass has been temporarily
disabled.
BATTERY IN DISCHARGE Battery is near end of autonomy. Shutdown the load connected to UPS
before the UPS switches itself off to protect
its batteries.
MANUAL BYP IS CLOSED Maintenance Bypass closed. Load
supplied by mains.
This alarm is only displayed if the UPS is
on Maintenance Bypass.
Uninterruptible Power Supplies Ltd.
Woodgate
Bartley Wood Business Park
Hook
Hampshire
RG27 9XA
Tel: 01256 386700
0800 731 3269 (24 Hr.)
Fax: 01256 386701
Email: service@upspower.co.uk

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uninterruptible Power Supplies PowerWave 3000T and is the answer not in the manual?

Uninterruptible Power Supplies PowerWave 3000T Specifications

General IconGeneral
BrandUninterruptible Power Supplies
ModelPowerWave 3000T
CategoryUPS
LanguageEnglish