PID UG2001-2050 SERIES
Diesel Generator Set
OPERATIONS AND SERVICE
For
69UG15
Generator Set Units
T-360 Rev G

Table of Contents

Questions and Answers

  • T
    Timothy BoltonSep 23, 2025
    What to do if low output voltage measured across United Technologies Carrier Transicold 69UG15 Inverter charger output?
    • W
      whawkinsSep 23, 2025
      If you measure low output voltage across the charger output of your United Technologies Inverter, check charging leads from charger to battery.
  • T
    Theresa ColemanAug 25, 2025
    Why is my United Technologies Carrier Transicold 69UG15 overheating?
    • M
      Mr. John CarpenterAug 25, 2025
      If your United Technologies Inverter is overheating, several factors could be responsible. The generator might be overloaded, so check it. Clogged vents or baffles could be the cause, so inspect and clean them. Insufficient air circulation or recirculation can also lead to overheating, so check and clean the area. An unbalanced load may contribute to overheating, so balance the load. Finally, a dry bearing can cause this issue, so replace it.
  • A
    Anita McdanielAug 25, 2025
    What to do if United Technologies Carrier Transicold 69UG15 starter motor cranks, but fails to start?
    • J
      joel29Aug 26, 2025
      If the starter motor cranks but the United Technologies Inverter fails to start, consider these possibilities: There might be water inside the fuel system, in that case drain the sump. The fuel filters could be plugged, so replace them. Fuses F1, F2, F3, and F4 might be bad, so check and replace them. There may be a loose or no connection between the wire harness and the Electronic Governor Module (EG), so check and correct the connection.
  • C
    Christian YatesAug 27, 2025
    Why does my United Technologies Inverter engine start then stop?
    • M
      mackenzieburgessAug 27, 2025
      If your United Technologies Inverter engine starts and then stops, here are a few things to investigate: Check for an open wiring circuit to the fuel solenoid and inspect for leaks in the fuel system. The fuel solenoid itself might be defective, so replace it.
  • P
    Patrick OdonnellAug 27, 2025
    How to troubleshoot no voltage in United Technologies Inverter?
    • T
      Timothy CameronAug 27, 2025
      If there is no voltage in your United Technologies Inverter, consider the following: There may be loss of rotor magnetism, in that case replace it. The circuit breaker may have tripped, so check CB1. There may be an open in stator windings or a short circuit, so replace it. The drive gear could be worn or stripped, so check and replace it. The contactor might not be engaged, so replace it.
  • K
    Katherine WuSep 13, 2025
    What happens if reverse polarity connection to battery has caused charger to stop charging on United Technologies Carrier Transicold 69UG15?
    • H
      Hannah HolderSep 14, 2025
      If a reverse polarity connection to the battery has caused the charger to stop charging on your United Technologies Inverter, replace it.
  • C
    Christopher CunninghamSep 12, 2025
    What to do if nothing happens when Ignition switch is placed in the RUN position on United Technologies Inverter?
    • A
      Ashley ThompsonSep 12, 2025
      If nothing happens when you place the ignition switch in the RUN position on your United Technologies Inverter, and no lights illuminate, try the following: Tighten the loose connector on the module. Check for 12 volts at Pin 4/Replace module if the auto restart module is bad. Check and correct the wiring if there are mis-wired connectors.
  • D
    daisy50Sep 12, 2025
    What to do if alarm sounds, but engine does not crank on United Technologies Inverter?
    • A
      Amy HuffmanSep 13, 2025
      If the alarm sounds, but the engine does not crank on your United Technologies Inverter, trace and correct if there is no voltage at Pin 2 of the connector. Replace module if the auto restart module is bad.
  • E
    Edward BoothSep 4, 2025
    What causes United Technologies Inverter starter not to disengage after engine starts?
    • K
      Kathy MurraySep 4, 2025
      If the engine starts, but the starter does not disengage on your United Technologies Inverter, check and correct the speed sensor wiring if it is loose. If the wiring is not the issue, the speed sensor itself may be bad, so replace it. The auto restart module could also be the problem, so replace the module.
  • S
    stephaniehudsonSep 2, 2025
    What to do if United Technologies Carrier Transicold 69UG15 engine will not shut off?
    • W
      wjohnsonSep 2, 2025
      If your United Technologies Inverter engine will not shut off, it could be due to a loose ground connection, so clean and tighten it. Alternatively, the fuel solenoid may be improperly seated, so correct it.