FIRST TIME CONTROL SETUP
SECTION B, PAGE 9
B6. ENTERING THE CYLINDER AREA:
After entering the air cylinder area into the display:
Push The display will now show:
B7. FORGE DELAY: This is a fairly uncommon function on welders. But if
your welder has an extra solenoid valve and pressure regulator for BACKUP
(sometimes called BUCKING) PRESSURE, enter the air pressure that you will set
on that pressure regulator. A typical value is 20psi.
If you do not have this FORGE DELAY system installed on your welder, leave the
value at 00.
Press and the display will show:
If you disconnect the air coming into the welder and
the electrodes do not close by gravity, press:
and skip to B8.
But be sure that whatever you enter into this display for BACK-UP
PRES. will match what you set on the BACK-UP pressure regulator on
the welder. Otherwise all of the TIP FORCE calculations will be
incorrect.
Area of CYLINDER is
00.0 SQUARE INCHES
After entering data
Press YES
For FORGE DELAY:
BACKUP PRES.= 00 PSI
After entering data
Press YES
HEAD WEIGHT = 000LB
Want to change? PUSH
The YES or NO button