EasyManua.ls Logo

Universal ECO Series - User Manual

Default Icon
5 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
3267 Grapevine St | Mira Loma, CA 91752 | T: (888) 866-4765 | F: (888)
806-5557
Low Voltage Power Module Installation & Instruction Manual
ECO SERIES TRANSFORMERS
IMPORTANT SAFETY INSTRUCTIONS
WARNINGS:
THIS POWER UNIT MUST BE CONNECTED TO A COVERED GFCI RECEPTACLE MARKED WET
LOCATION” WHILE IN USE
CAUTION: FOR USE ONLY ON A BRANCH CIRCUIT PROTECTED BY A CLASS A TYPE GROUND
FAULT CIRCUIT INTERRUPTER
FOR USE WITH LANDSCAPE LIGHTING SYSTEMS ONLY - LANDSCAPE LIGHTING SYSTEMS ARE FOR
OUTDOOR USE ONLY (NOT FOR USE IN DWELLING UNITS)
THIS DEVICE IS ACCEPTED AS A COMPONENT OF A LANDSCAPE LIGHTING SYSTEM WHERE THE
SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY CSA OR LOCAL INSPECTION
AUTHORITIES HAVING JURISDICTION
DO NOT CONNECT TWO OR MORE POWER SUPPLIES IN PARALLEL
DO NOT MOUNT POWER SUPPLY OR FIXTURES WITHIN 3 METERS (10 FEET) OF A SWIMMING
POOL OR SPA
DO NOT USE AN EXTENSION CORD WITH THIS POWER SUPPLY
Sizing Transformer
The total wattage (W) - or volt-amps (VA) for LED - of all of the fixtures operated by this transformer
must not exceed the wattage rating of the transformer.
If you are powering halogen lamps, calculate the load by adding the wattage of the lamps in the system.
Make sure the load does not exceed the wattage rating of the transformer.
If you are powering LED lamps or fixtures, calculate the load by adding the volt/amp (VA) values of all of
the lamps in the system. VA is calculated using the following formula:
VA =
Wattage
Power Factor
RISK OF SHOCK. Install power unit at least 5 feet
from a pool or spa and at least 10 feet from a
fountain. Where the power unit is installed within
10 feet of a pool or spa, connect unit to a
GFCI protected branch circuit.
RISK OF ELECTRIC SHOCK. Install power
unit at least 5 feet from a pool, spa or
fountain.
Where the power unit is installed (a) indoor
within 10 feet of a pool, spa, or fountain, or
(b) outdoor, connect power unit to a
receptacle protected by a GFCI.
Question and Answer IconNeed help?

Do you have a question about the Universal ECO Series and is the answer not in the manual?

Summary

General Safety Instructions

Risk of Shock Warnings

Install power units at least 5 feet from water; connect to GFCI if within 10 feet.

Electrical and Installation Precautions

Connect to GFCI, use Class A GFCI breaker, for outdoor landscape use only, no parallel supplies.

Transformer Sizing and Load Calculation

Calculating System VA for LEDs

Calculate load by adding VA values for LEDs; use 0.7 Power Factor if unknown.

Transformer Unit Mounting

Mounting Location and Method

Mount on a solid, flat surface, 12 inches from ground, within 6 feet of GFCI receptacle.

System Connections and Checks

Connecting Secondary Wires to Transformer

Connect low voltage wires to common and voltage taps using a flathead screwdriver.

Checking Fixture Voltage and Output Amps

Verify fixture voltage is within range and output current is below rated amperage.

System Performance and Optimization

Determine System Load and Voltage Drop

Understand voltage drop factors (distance, wattage, wire gauge) and how to minimize it.

Determine Input Amps

Measure input current using a clamp-on meter and ensure it's below the transformer's rated input current.

Timer Module Operation

Countdown Timer Module Functionality

Learn how to operate the timer module for automatic lighting control, including ON/OFF and dusk-to-dawn settings.

Summary

General Safety Instructions

Risk of Shock Warnings

Install power units at least 5 feet from water; connect to GFCI if within 10 feet.

Electrical and Installation Precautions

Connect to GFCI, use Class A GFCI breaker, for outdoor landscape use only, no parallel supplies.

Transformer Sizing and Load Calculation

Calculating System VA for LEDs

Calculate load by adding VA values for LEDs; use 0.7 Power Factor if unknown.

Transformer Unit Mounting

Mounting Location and Method

Mount on a solid, flat surface, 12 inches from ground, within 6 feet of GFCI receptacle.

System Connections and Checks

Connecting Secondary Wires to Transformer

Connect low voltage wires to common and voltage taps using a flathead screwdriver.

Checking Fixture Voltage and Output Amps

Verify fixture voltage is within range and output current is below rated amperage.

System Performance and Optimization

Determine System Load and Voltage Drop

Understand voltage drop factors (distance, wattage, wire gauge) and how to minimize it.

Determine Input Amps

Measure input current using a clamp-on meter and ensure it's below the transformer's rated input current.

Timer Module Operation

Countdown Timer Module Functionality

Learn how to operate the timer module for automatic lighting control, including ON/OFF and dusk-to-dawn settings.

Overview

The Universal Lighting Systems ECO Series Transformer is a low-voltage power module designed for landscape lighting systems. It functions by converting standard household voltage to a lower, safer voltage suitable for outdoor lighting. This device is intended for outdoor use only and is not suitable for dwelling units.

Safety and Installation:

The transformer requires careful installation to ensure safety and proper operation. It must be connected to a covered GFCI receptacle marked "WET LOCATION" while in use. For conduit-connected power units, the transformer should be installed at least 5 feet from a pool or spa and at least 10 feet from a fountain. If installed within 10 feet of a pool or spa, it must be connected to a GFCI-protected branch circuit. For power supply cord-connected units, the transformer must be installed at least 5 feet from a pool, spa, or fountain. If installed indoors within 10 feet of a pool, spa, or fountain, or outdoors, it must be connected to a receptacle protected by a GFCI. It is crucial to use a branch circuit protected by a Class A type ground fault circuit interrupter. The device should not be mounted within 3 meters (10 feet) of a swimming pool or spa, and an extension cord should not be used with this power supply. Multiple power supplies should not be connected in parallel.

To mount the transformer unit, first remove the transformer door for access. Find a solid, flat surface for mounting, ensuring it is at least 12 inches between the terminals and ground level, with wire terminals facing down. The mounting location should also be six feet or fewer from a 120V supply circuit protected by a Class A type ground fault circuit interrupter. Load-bearing screws or wall anchors should be inserted into pre-drilled holes that align with the keyhole slots on the transformer's mounting brackets. Finally, secure the transformer's keyhole slots to the screws or wall anchors.

Wiring and Voltage Management:

Connecting secondary wires to the transformer involves several steps. Begin by removing the bottom plate from the transformer. Use a flathead screwdriver to adjust the common tap and the appropriate low voltage tap on the terminal lug to accept secondary wires. Route the secondary wire cables through the knockouts in the bottom plate. Separate the wires from each pair and strip approximately one inch from both ends. Connect one wire from each pair to the common tap and the other wire to the appropriate low voltage tap. Secure the wires by tightening the common tap and the low voltage taps with a flathead screwdriver.

It is essential to check the voltage at each fixture to ensure it falls within the input voltage range of the lamp or fixture. Halogen lamps and some LEDs typically have a 12V input voltage rating. If the specified input voltage range is 12V, the input voltage to the fixture must be between 11V and 12V. Voltages exceeding 12V may increase light output but reduce average rated life, while voltages below 11V may decrease light output but extend average rated life. Many LEDs have wider input voltage ranges, such as 10V-15V or 10V-18V, and any voltage within this range is acceptable. To check the voltage, plug the transformer into a covered 120V GFCI receptacle, switch it on, and use a voltmeter to measure the voltage at each fixture. If the measured voltage is outside the acceptable range, adjust it by moving the wire to a higher or lower voltage tap.

After checking voltages, measure the output current on the low voltage cable at the transformer for each circuit using a clamp-on meter. Ensure the output current is below the maximum rated amperage for the circuit size.

Sizing and Load Calculation:

Properly sizing the transformer is critical. The total wattage (W) or volt-amps (VA) of all fixtures must not exceed the transformer's wattage rating. For halogen lamps, calculate the load by adding the wattage of each lamp. For LED lamps or fixtures, calculate the load by adding the volt/amp (VA) values of all lamps using the formula: VA = Wattage / Power Factor. If the power factor of the LEDs is unknown, use 0.7 for the calculation. It is recommended to select a transformer with excess capacity to accommodate future additions.

Voltage Drop Management:

Voltage drop occurs along the secondary wire and is influenced by the distance of the run, the total wattage of the system, and the wire gauge. Fixtures further from the transformer will receive lower voltage. To minimize voltage loss, thicker wire (lower gauge number) is recommended, such as 8/2, 10/2, or 12/2 wire. Spreading the load across separate wire runs and effective system wiring can also help minimize voltage drop.

Input Amps Measurement:

The unit includes a looped wire attached to the optional photocell plug, which can be used with a clamp-on meter to measure the input current. Ensure the input current of the system remains below the maximum rated input current for the transformer. If it exceeds the maximum rating, fixtures should be removed or lamp wattages reduced until the input current is acceptable.

Countdown Timer Module & Photocell Operation:

The transformer includes a countdown timer module and photocell. The circuit breaker will trip if there is a short circuit or if the total lamp wattage exceeds the transformer's rated wattage. To reset the breaker, the issue causing the trip must first be resolved, then push the "reset" button. If the breaker trips again, check for overload or short circuit.

The timer can be operated using the reset button, photocell, digital display screen, and up/down arrow buttons.

  • "Off" means no display.
  • "On" or "0" means the lights are always ON.
  • "Auto" or "A" means the lights turn on at Dusk and off at Dawn.
  • Settings 1 through 9 (e.g., 1,2,3,4,5,6,7,8,9) mean the lights turn on at Dusk and off after 1, 2, 3, 4, 5, 6, 7, 8, or 9 hours, respectively. The timer will stop and reset if the unit is exposed to 30 seconds of light during a countdown. After a full countdown is completed, the unit will reset only after 1 hour of exposure to lights. The timer module is field replaceable and covered under warranty for 1 year.

Universal ECO Series Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureNEMA 3R
CategoryTransformer
SeriesECO
Insulation ClassH
StandardsUL Listed, cUL Listed