Vaillant Training/Logical Fault Finding Guide for all
COMBlcompact and THERMOcompact models
v
t
v
~Vaillant
HEATING,CONTROLS,HOTWATER.
Question and Answer IconNeed help?

Do you have a question about the Vaillant COMBlcompact VCW 242E and is the answer not in the manual?

Vaillant COMBlcompact VCW 242E Specifications

General IconGeneral
MountingWall-mounted
Output24 kW
Fuel TypeNatural Gas
Max working pressure3 bar
TypeCombi
Boiler TypeCombi

Summary

Guidance Notes

Front Control Panel Overview

Details the components and functions of the front control panel, including indicator lights and switches.

Room Sealed Fan Flued Models (RSF)

Power Supply and Fuse Checks

Verifies the 240v AC supply and checks appliance fuses for continuity and operation.

Fan Operation Checks

Diagnoses fan issues by checking reset buttons, potentiometer, time delay, fuses, thermostats, and NTC sensors.

Pump Operation Checks

Assesses pump functionality by checking voltage, rotation, and external control signals.

Ignition Attempt Checks

Troubleshoots ignition failures by checking microswitches, fan pressure switch, flue installation, and fan operation.

Burner Ignition and Stability Checks

Investigates burner light and stability issues, checking gas supply, differential valve, gas operator, and spark generator.

Burner Modulation (High Fire) Checks

Diagnoses issues with burner modulation to high fire rate, checking gas pressure and diaphragm pump.

DHW Operation Checks (VCW)

Verifies domestic hot water operation for VCW models, checking demand, water section, microswitch, and diverter valve.

Balanced Flue and Open Flue Models

Pilot Light Establishment Checks

Troubleshoots pilot light issues by examining gas supply, injector, ignitor, thermocouple, and overheat thermostat.

Power Indicator and Fuse Checks

Checks for correct operation of the main power switch neon and verifies appliance and spur fuses.

Pump Operation Verification

Confirms pump operation by checking voltage, rotation, and availability of power for external controls.

Hydraulic Operation Checks

Assesses hydraulic system integrity, checking diverter valve, differential valve, and system pressure.

Burner Lighting Checks

Diagnoses burner lighting failures by checking potentiometer, time delay, overheat thermostats, NTC sensor, and microswitches.

Burner Modulation (Low Fire) and Shut-off Checks

Evaluates burner modulation to low fire and shut-off, testing NTC/electronic board and gas operator.

Related product manuals