Valent Controls IOM 39 IOM-C1-0616
Part Number 474626
7.Heating w/Energy Recovery 8.Dehumidifying 9.Off
10.Shutdown Delay
Air Flow Monitoring Station CFM 2
Energy Recovery Control Output
Energy Recovery Defrost Mode. True = Defrost
Allows BAS to override the supply fan signal. *
Allows BAS to override the exhaust fan signal. *
Allows BAS to override the outdoor air damper
signal. *
WSHP Refrigerant Low Pressure Alarm
Space Unoccupied Cooling Setpoint
Space Unoccupied Heating Setpoint
Space Unoccupied Humidity Setpoint
Occupancy Mode 1.Unocc Off 2.Unocc Cooling
3.Unocc Heating On 4.Unocc Dehum 5.Occupied On
6.Occupied Auto 7.Shutdown
Space Temperature Setpoint Offset
Space Temperature Cooling Setpoint
Space Temperature Heating Setpoint
Air Flow Monitoring Exhaust Cone Flow
Allows BAS to disable local setpoint adjust
Outside Air Damper Minimum Position
Active Space Temperature Setpoint