When the duct is situated in a warm indoor space, 20-mm closed-cell insulation
against condensation enables the fl ow of supply air cooler than the dew point in
the duct.
The condensing water pipe must have a downward slope.
The pipe must never be connected directly to the drain.
MLV Multi 200: Water seal height ca. 50…100 mm.
Connection pipes Cu 18 or Cu 22, depending on the length
of the pipes. The pipes are covered with 20-mm insulation
against condensation.
The air bleeder is always mounted at the highest point in the network.
The fi lter must always be located before the radiator.
In the outdoor duct, 20-mm closed-cell insulation against condensation.
HEAT PUMP
SUPPLY AIR
OUTDOOR AIR
VENTILATION UNIT
RADIATOR PART
SENSOR
GROUND COLLECTOR