Troubleshooting Guide
Electric Actuators with DPS Positioner
5610/5616 Series
IOM
5610
5616
TSG DPS
PROBLEM POSSIBLE CAUSE SOLUTION
Actuator fails to operate and condensaon
or water is found inside the actuator
DIN plug connectors are loose, missing or have
damaged seals. Connector seals installed
incorrectly.
Inspect seals and replace if necessary. Make sure
seals are installed correctly and ghten DIN
connector screws securely (0.4 to 0.5Nm).
Built in heater was not acvated connuously Power must be maintained ‘ON’ to acvate
internal heater. This heater will help prevent
condensaon buildup inside the actuator. If the
actuator has failed due to excessive condensaon
or water inside the actuator, replace with a new
actuator.
Actuator fails and excessive black dust
and/or corrosion is found under the red
cover
Excessive condensaon or water inside
actuator. Highly corrosive environment,
saltwater, chemicals, other.
If the actuator has failed due to excessive black
dust or corrosion inside the actuator, typically it is
non-repairable and must be replaced with a new
actuator.
Black dust from motor brush wear may be
caused by exceeding the 75% duty rang of the
actuator.
Actuator must operate within the 75% duty cycle
rang. Typically, this means the motor can be
running for 45 seconds, then must be o for 15
seconds of each minute.
Actuator is worn out Replace with a new actuator
No output signal from posion
conrmaon limit switches
Switches are wired incorrectly Check the switch wiring and make sure the
common for limit switches is on PIN 1. If checking
connuity, you should have connuity between
PIN 1 and 2 when actuator is closed and
connuity between PIN 1 and 3 when open. No
connuity when actuator is moving in between
closed and open posions.
Exceeding the current capacity has damaged
the limit switch. Switch rang 3 amps @
125/250VAC, 30VDC resisve load.
Damage to the limit switches is not a eld
repairable item. Either return actuator to the
factory for possible repairs or replace with a new
actuator.
Limit switch cams are out of adjustment. Limit switch cams can be adjusted if necessary.
Contact customer service for Service Procedure.
Manual Override
Selector Lever
MAN: Manual Mode
AUTO: Automac Mode
Visual Posion
Indicator (shown in
open posion)
LED Power On and
Diagnosc Light
Manual Override
Knob
DIN Plug Connectors