Troubleshooting Guide
Electric Actuators with DPS Positioner
5610/5616 Series
IOM
5610
5616
TSG DPS
Electrical Wiring Diagram for 5610/5616 series
Actuators with DPS Posioner
DIN Plug Connectors
1. Seal
2. Screw terminal block (Pins 1, 2, 3 & G)
3. Connector housing
4. Retainer screw
5. Cable retainer gland
Wiring: Main Power Connecon
Power is connected to the actuator via the
large gray DIN plug connector. Wires are
connected to screw terminals located inside
the connector.
Power: connect to PIN 1 and PIN 2
Ground: connect at pin on DIN connector to
earth ground
Notes:
1. The Neutral (AC voltages) or Negave (DC voltages
must be connected to PIN 1.
2. Power should be maintained to acvate the
internal heater. This heater will help prevent
condensaon build up inside the actuator.
3. Actuator should have it’s own fused and isolated
circuit. Do not connect actuators in parallel or on the
same circuit with other equipment.
4. Supply voltage to 24 volt actuators should not
exceed 25.2 volts (24 volts +5%).
Wiring: Analog Control Signal
Signal Input:
Connect Negave (-) input to PIN 1
Connect Posive (+) input to PIN 2
Signal Output (posion monitoring signal):
Connect to PIN 3
Note: The signal output (use of output is oponal) will
be in the same format as the input. ex: 4-20mA input,
4-20mA output or 0-10v input, 0-10v output. Nominal
impedance 100 ohms (4-20mA), 13K ohms (0-10v). Do
not connect ground PIN on control signal plug.
Wiring: Posion Conrmaon Limit
Switches
Two auxiliary dry contact limit switches are
provided to conrm the valve open and closed
posion. Use of these switches is oponal.
Limit Switch Rang 3A@125/250 VAC, 30VDC
resisve load
PIN 1: Common
PIN 2: Signal to conrm Closed Posion
PIN 3: Signal to conrm Open Posion
Note: Using the posion conrmaon switches is
oponal and not required for actuator to funcon
correctly.
Before connecting
power, confirm
correct voltage is
being applied
Wiring I.D. for Optional Prewired DIN Cables
PIN 1 - Brown PIN 3 - Black
PIN 2 - Blue GROUND - Green/Yellow
1 2
Power Connecon
LS1
OPEN
Signal
LS2
CLOSED
Signal
Posion Conrmaon
Limit Switches
1 2
3
N / -
L / +
LS1
N / -
LS2
N / -
COM
L / +
Earth
Ground
DPS Posioner
2 1
3
+ -
Input
+
Output
Power
VAC or VDC
Power Plug
Signal Input
Posion Switches