7
LAF
Electrical connections
Connect the electric cable to an earthed 230V power outlet. Requisite fuse: See overview of range.To start the LAF 50-150 dehumi-
dier, set the switch to position I (see Fig. C). e electronic control system delays start by about 5 seconds.
Fig. C Fig. D
e LAF 50E-150E dehumidiers incorporate an electric heater and a two-position switch (see Fig. D).
Position I Dehumidication
Position II Dehumidication + heating
e electric heater will be switched o when the preset room temperature has been reached (set at the factory to 21°C).
e value can be adjusted on the electronic circuit board to between 10°C and 26°C (see the arrow in Fig. E), which should be
carried out by a specialist.
Fig. E
If the ambient temperature is lower than +3°C or higher than +30°C, the dehumidier will be stopped (indicated by the LED). It
will restart automatically when the temperature rises to 5-6°C resp. sinks to 27-28°C. If frost should occur on the evaporator, the
dehumidier will be automatically defrosted once an hour.
LED indications
Steady light the collecting container is full and should be emptied.
Two ashes in sequence Ambient temperature too high (see above).
ree ashes in sequence Ambient temperature too low (see above).
Four ashes in sequence Room temperature sensor faulty (summon a service technician).
Five ashes in sequence Defrosting sensor faulty (summon a service technician).