EasyManuals Logo

Vector TCI-W11 Series Overview

Vector TCI-W11 Series
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
TCI-W Universal Controller
CONTROL LOOP CONFIGURATION
Doc: 70-00-0158, V1.4-20220321 © Vector Controls GmbH, Switzerland Page 11
Subject to alteration
Legend
T, U Input signal temp/universal
X
PH
P-band heating/direct
X
PC
P-band cooling/reverse
X
DZ
Dead zone h/c set points
X
SBY
Economy mode set point shift
W
H
Set point heating/reverse
W
C
Set point cooling/direct
Y
H1,
Y
R1
PI sequence heating/reverse
Y
C1,
Y
D1
PI sequence cooling/direct
PI control sequence
Parameter
Description
Range
Default
1L 09
Offset for heating PI sequence
per input
0
1L 10
Offset for cooling PI sequence
per input
0
1L 11
P-band heating
per input
2.0°C(4.0°F)
1L 12
P-band cooling
per input
2.0°(4.0°F)
1L 13
Integral gain heating (0.1 steps)
low= slow reaction, high= fast reaction
025.5
0.0
1L 14
Integral gain cooling(0.1 steps)
025.5
0.0
1L 15
Measuring interval integral (seconds)
low= fast reaction, high value= slow reaction
0255
1 sec.
Proportional control(P-band)
The proportional control function calculates the output based on the difference between setpoint and measured value.
The proportional band (P-band) defines the difference between setpoint and measured value which will result in a 100%
output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-band value, at 10v the
controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the proportional control sequence.
Setting the proportional band to 0 disables proportional control.
Integral and Differential control
Proportional control is in most cases a very stable control mode. The flaw of proportional control alone, however, is
that the setpoint is normally not reached. As the measured value gets closer to the setpoint, the output reduces until
it reaches a point, a fraction above or below the setpoint, where the output equals the load. To reach the setpoint and
achieve a higher level in comfort the Integral/Differential function should be activated.
Integral Gain (KI)dynamically increases the output by the selected KI value every Measuring Interval TI until the
setpoint is reached. The challenge is to prevent hunting, where the output increases too fast, the temperature
overshoots the setpoint, the output goes to 0, the temperature undershoots the setpoint, and the cycle repeats itself.
Hunting may result if the integral gain is too high or measuring interval too short. Each system is different. To
prevent instability the P-band should be extended when integral gain is active (L14 or L15 set above 0).
Setting the integral gain to 0 disables integral and differential control.
Recommended Values
heating (air)
heating (radiant)
humidifying
cooling
dehumidifying
pressure
P-band
23°C(46°F)
11.5°C(23°F)
Measuring interval (TI)
2
5
15
1
70
1
Integral gain (KI)
0.2
0.1
0.1
0.2
0.3
0.8
Heating/Reverse
Cooling/Direct
100
0
T [°C, F]
U [V, mA]
Y
H1
, Y
R1
X
PH
W
H
X
PC
X
DZ
Y
C1,
Y
D1
W
C
X
SBY
X
SBY

Other manuals for Vector TCI-W11 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TCI-W11 Series and is the answer not in the manual?

Vector TCI-W11 Series Specifications

General IconGeneral
BrandVector
ModelTCI-W11 Series
CategoryController
LanguageEnglish

Related product manuals