AC310 Series Frequency AC Drive Manual
I
Contents
1 OVERVIEW ................................................................................................................................................ 1
1.1 SAFETY PRECAUTIONS ........................................................................................................................... 1
1.2 BEFORE USE ........................................................................................................................................... 1
1.3 TECHNICAL SPECIFICATIONS .................................................................................................................... 3
2 INSTALLATION .......................................................................................................................................... 4
3 KEYBOARD LAYOUT AND OPERATING INSTRUCTIONS .............................................................. 10
4 FUNCTION PARAMETER TABLE ......................................................................................................... 12
4.1 PARAMETER ICON DESCRIPTION ............................................................................................................ 12
4.2 PARAMETER CONTENT .......................................................................................................................... 12
4.3 ENVIRONMENT APPLICATION .................................................................................................................. 13
4.4 F01BASIC SETTINGS........................................................................................................................ 13
4.5 F02MOTOR PARAMETER .................................................................................................................. 16
4.6 F03VECTOR CONTROLLING ............................................................................................................. 18
4.7 F04 V/F CONTROLLING ................................................................................................................... 21
4.8 F05INPUT TERMINAL ........................................................................................................................ 22
4.9 F06OUTPUT TERMINAL .................................................................................................................... 25
4.10 F07 OPERATIONAL CONTROL ......................................................................................................... 29
4.11 F08AUXILIARY CONTROL ................................................................................................................ 31
4.12 F09RESERVED ............................................................................................................................... 32
4.13 F10PROTECTION PARAMETER ........................................................................................................ 32
4.14 F11OPERATOR PARAMETER ............................................................................................................ 35
4.15 F12COMMUNICATION PARAMETER .................................................................................................. 37
4.16 F13PROCESS PID CONTROL .......................................................................................................... 39
4.17 F14:MULTI-SPEED AND SIMPLE PLC .................................................................................................... 41
4.18 C0XMONITORING PARAMETER ........................................................................................................ 44
4.19 TERMINAL SELECTION FUNCTION ......................................................................................................... 45
4.20 FAULT AND WARNING CODE TABLE ....................................................................................................... 46
5 INSPECTION, MAINTENANCE AND GUARANTEE ........................................................................... 48
5.1 INSPECTION .......................................................................................................................................... 48
Question and Answer IconNeed help?

Do you have a question about the Veichi AC310 Series and is the answer not in the manual?

Veichi AC310 Series Specifications

General IconGeneral
Rated Voltage380V AC
Input Voltage3-phase 380V AC ±15%
Power Range0.75kW-630kW
Control ModeV/F control, vector control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, overvoltage, undervoltage, overload, overtemperature, phase loss, short circuit
Communication InterfaceRS485, Modbus RTU
Operating Temperature-10°C to +50°C
Storage Temperature-20℃~+60℃
Humidity5%~95%, non-condensing
AltitudeBelow 1000m (Derating if altitude exceeds 1000m)

Summary

1 Overview

1.1 Safety Precautions

Provides essential safety rules and warnings for operating the AC Drive to prevent injury or damage.

1.2 Before use

Instructions for checking the product's integrity upon receipt and opening the outer packaging.

1.3 Technical specifications

Details specifications for power input, output, control modes, speed, torque, and various basic functions.

4.3 Environment application

F00.00 Parameter access level

Sets the parameter access level based on restricted access cases for V/F, SVC, FVC, PMVF, PMSVC, PMFVC modes.

F00.03 Initialization

Sets the AC Drive initialization method, including options for no initialization, purpose-based, all parameters, or clearing faults.

4.4 F01: Basic Settings

F01.00 Motor control

Defines the motor control mode, supporting Asynchronous and Synchronous motor control types.

F01.01 Run command channel

Selects the channel for run/stop commands and direction, supporting keyboard, terminal, RS485, and option cards.

F01.02 Frequency given channel A

Specifies the source channel for frequency conversion, supporting keyboard, analog inputs, and communication.

F01.20 Acceleration/deceleration time reference

Sets the reference frequency for calculating acceleration/deceleration time based on maximum, fixed, or set frequency.

F01.21 Acceleration time unit

Defines the unit for acceleration time setting, with options for seconds (s), tenths of a second (0.1s), or hundredths of a second (0.01s).

F01.22 Acceleration time 1

Sets the time for output frequency to accelerate from 0.00 Hz to the reference frequency.

F01.31 S curve acceleration and deceleration selection

Enables or disables S curve acceleration and deceleration for smoother motion profiles.

F01.40 The carrier frequency

Sets the switching frequency of the AC Drive IGBT for PWM control.

F02.2x: Synchronous Motor Senior Parameter

F02.20 Synchronous stator resistance

Sets the PM stator resistance value for synchronous motor control.

F02.21 Synchronous machine D-axis inductance

Sets the D-axis inductance value for Permanent Magnet synchronous motors.

F02.22 Synchronous machine Q-axis inductance

Sets the Q-axis inductance value for Permanent Magnet synchronous motors.

F02.3x-F02.4x: Encoder Parameter

F02.30 Speed feedback encoder type

Selects the type of speed feedback encoder, supporting normal ABZ or rotary transformer.

F02.31 Encoder direction

Sets the direction of the encoder, determining if it matches or opposes the motor rotation.

F02.35 Encoder speed measurement filter time

Sets the filter time for the encoder speed measurement, used to smooth feedback signals.

F03.1x: Torque Optimization Controlling

F03.12 Current loop Q-axis proportional gain

Sets the proportional gain for the current loop's Q-axis control.

F03.15 Electric state torque limit

Sets the torque limit based on the motor's operating state.

F03.3x: Magnetic Flux Optimization

F03.30 Weak magnetic feed forward coefficient

Sets the coefficient for weak magnetic feed forward control.

F03.31 Weak magnetic control gain

Sets the gain for the weak magnetic control loop.

F03.38 Energy-saving operation excitation lower limit

Sets the lower limit for excitation current in energy-saving operation mode.

4.7 F04 : V/F Controlling

F04.00 Linear VF curve selection

Selects the type of V/F curve to match different load characteristics.

F04.01 Torque boost

Configures automatic or manual torque boost to improve low-speed torque.

F04.02 Torque boost cutoff frequency

Sets the frequency limit for the torque boost function to be active.

F04.05 Slip compensation filter time

Sets the filter time for slip compensation to improve parameter learning and results.

F04.1x: Custom V/F Curve

F04.10 Self-setting voltage V1

Sets the self-setting voltage V1 for custom V/F curve configuration.

F04.11 Self-set frequency F1

Sets the self-set frequency F1 for custom V/F curve configuration.

F05.0x: Detection Delay

F05.10 X1 effective detection delay

Sets the delay time for input terminal X1 transit from inactive to active state.

F05.11 X1 invalid detection delay

Sets the delay time for input terminal X1 transit from active to inactive state.

F05.2x: Terminal Movement Selection

F05.20 Terminal control mode

Selects the terminal control mode, supporting two-wire and three-wire systems.

F05.25 Terminal UP/DW control selection

Selects UP/DW terminal control for frequency storage on power down or adjustable during stop.

F05.27 Terminal emergency stop deceleration time

Sets the deceleration time for the terminal emergency stop function.

F05.5x: AI2 Setting

F05.58 AI2 upper limit corresponding setting

Sets the percentage of the corresponding set value for AI2 upper limit.

F05.59 AI2 filter time

Defines the analog signal filter time to eliminate interfering signals for AI2.

F05.6x: Curve 1 Parameters

F05.60 Curve 1 lower limit

Sets the lower limit value for Curve 1.

F05.63 Curve 1 inflection point 2 input voltage

Sets the input voltage for the second inflection point of Curve 1.

F05.67 Curve 1 upper limit

Sets the upper limit value for Curve 1.

F05.7x: Curve 2 Parameters

F05.70 Curve 2 lower limit

Sets the lower limit value for Curve 2.

F05.74 Curve 2 inflection point 2 input voltage

Sets the input voltage for the second inflection point of Curve 2.

F05.77 Curve 2 upper limit

Sets the upper limit value for Curve 2.

F06.4x: Frequency Detection

F06.40 Frequency detection value 1

Sets the first frequency detection value.

F06.42 Frequency detection value 2

Sets the second frequency detection value.

F06.5x: Monitor parameter comparator output

F06.50 Comparator 1 monitor selection

Selects the monitor parameter for Comparator 1, using units and digits.

F06.51 Comparator 1 upper limit

Sets the upper limit value for Comparator 1.

F06.55 Comparator 2 monitor selection

Selects the monitor parameter for Comparator 2, using units and digits.

F06.56 Comparator 2 upper limit

Sets the upper limit value for Comparator 2.

4.10 F07: Operational Control

F07.00 Start mode

Selects the start mode, including start frequency, DC braking, or speed tracking.

F07.01 Start pre-excitation time

Sets the pre-excitation time for asynchronous motors without PG.

F07.02 Starting frequency

Sets the starting frequency below which the drive remains in standby.

F07.1x: Stop Control

F07.10 Stop mode

Selects the stop mode: deceleration stop or free stop.

F07.11 Shutdown detection frequency

Sets the frequency threshold for entering the stop state upon shutdown.

F07.12 Stop and restart limit time

Sets the waiting time after restarting from a shutdown state.

4.11 F08: Auxiliary Control

F08.00 Counter input source

Selects the source for the counter input, such as X terminal or PUL terminal.

F08.01 Count input frequency division

Sets the input frequency division for the counter function.

F08.02 Counter maximum

Sets the maximum value for the counter.

F08.3x: Swing Frequency Control

F08.30 Swing frequency control

Enables or disables the swing frequency control function.

F08.31 Swing frequency amplitude control

Sets the swing frequency amplitude control parameters.

F08.32 Swing frequency preset frequency

Sets the preset frequency value for swing frequency control.

F10.1x: Auxiliary Protection

F10.15 Energy consuming braking action voltage

Sets the voltage threshold for engaging the energy consuming braking action.

F10.16 Bus undervoltage suppression

Configures bus undervoltage suppression to adjust frequency and prevent faults.

F10.17 Bus undervoltage suppression point

Sets the bus voltage value to trigger the undervoltage suppression function.

F10.2x: Auxiliary Protection

F10.20 Input and output phase loss protection options

Enables input and output phase loss protection functions.

F10.22 Ground short circuit protection option

Enables ground short circuit protection for output and cooling fan.

F11.0x: Operator Parameter

F11.00 Key lock selection

Selects the key lock mode for the operator interface, including parameter modification and button locks.

F11.01 Key lock password

Sets a password to lock the keyboard functions, preventing unauthorized access.

F10.5x: Fault Recovery Protection

F10.50 Fault self-recovery times

Sets the allowable number of times the fault self-recovery function can be activated.

F10.51 Fault self-recovery interval

Sets the waiting time from when a fault occurs until the system attempts self-recovery.

F11.2x: Monitoring Parameter

F11.20 Keyboard display item settings

Configures which items are displayed on the keyboard, including frequency and power.

F11.21 Speed display factor

Adjusts the speed display factor for the C00.06 parameter.

4.15 F12: Communication Parameter

F12.00 Host-slave choice

Selects the communication mode: slave or host.

F12.01 Modbus communication address

Sets the communication address for Modbus, configurable for different slaves.

F12.02 Communication baud rate selection

Selects the communication baud rate for Modbus communication.

F13.00-F13.06: PID given and feedback

F13.00 PID controller given signal source

Selects the signal source for PID controller input, including keyboard, analog, or terminal.

F13.01 Keyboard digital PID given / feedback

Sets the keyboard digital PID given and feedback value.

F13.02 PID given change time

Sets the time duration for changing the PID given value.

4.17 F14:Multi-speed and Simple PLC

F14.00 Multi-speed 1

Sets the speed for PLC multi-speed step 1.

F14.01 Multi-speed 2

Sets the speed for PLC multi-speed step 2.

F14.02 Multi-speed 3

Sets the speed for PLC multi-speed step 3.

F14.31~F14.45: PLC Operation Direction and Time Selection

F14.31 PLC direction and acceleration and deceleration time of 1st stage

Sets PLC direction, acceleration, and deceleration time for the first stage.

F14.32 PLC direction and acceleration and deceleration time of 2nd stage

Sets PLC direction, acceleration, and deceleration time for the second stage.

C01: Fault Monitoring

C01.00 Fault type

Displays the type of the first fault that occurred.

C01.01 Troubleshooting information

Provides troubleshooting information related to the first fault.

C01.02 Fault operating frequency

Shows the operating frequency at the time the first fault occurred.

C02: Application Monitoring

C02.00 PID feedback

Displays the PID feedback value.

C02.01 PID given

Displays the PID given value.

C02.02 PID output

Displays the PID output value.