SI21 Solar Pump VFD Manual
33
F21.25(0x5519)
Minimum power
protection auto
restore working
time
0.0s3000.0s
10.0s
F21.26(0x551A)
Fault alarm restore
mode
0:Auto reset;1:Reset by manual
LED0:Low speed protection
LED1:Dry run
LED2:Over current protection
LED3: Minimum power protection
0000
F21.27(0x551B)
Water fulfilled
detect time
0.0s3000.0s
10.0s
F21.28(0x551C)
Water fulfilled
restore time
0.0s3000.0s
10.0s
F21.29(0x551D)
reserve
F21.30(0x551E)
DC current revise
offset
0.00A99.99A
0.01A
F21.31(0x551F)
DC current revise
proportion gain
0.0%999.9%
100.0%
F21.32(0x5520)
Power curve point 0
0.00kW99.99kW
0.50kW
F21.33(0x5521)
Power curve point 1
0.00kW99.99kW
1.00kW
F21.34(0x5522)
Power curve point 2
0.00kW99.99kW
1.50kW
F21.35(0x5523)
Power curve point 3
0.00kW99.99kW
2.00kW
F21.36(0x5524)
Power curve point 4
0.00kW99.99kW
2.50kW
F21.37(0x5525)
Flow curve point 0
0.0m³/h999.9m³/h
0.0m³/h
F21.38(0x5526)
Flow curve point 1
0.0m³/h999.9m³/h
5.0m³/h
F21.39(0x5527)
Flow curve point 2
0.0m³/h999.9m³/h
10.0m³/h
F21.40(0x5528)
Flow curve point 3
0.0m³/h999.9m³/h
15.0m³/h
F21.41(0x5529)
Flow curve point 4
0.0/h999.9m³/h
20.0m³/h
F21.42(0x552A)
Flow calculating
revise offset
0.0999.9
0.0
F21.43(0x552B)
Flow calculating
revise gain
0.0%999.9%
100.0%
F21.44(0x552C)
Power per day/
generated power
per day reset period
0.0h24.0h
7.0h
F21.45(0x552D)
Reserved