EasyManua.ls Logo

Velleman CU2200 - Alarm Setup - Input and SMS Configuration; Alarm Input Level and Alert Setup; Custom SMS Alarm Messages

Velleman CU2200
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CU2200_v5 VELLEMAN 7
b. Alarm Setup
Alarm Input Level & Alert Setup
Command: PWD:XXXX,ALMLEVELR:X,YY,ZZZZ,NNN%
XXXX Password
R Alarm channel number
X 0 means disabled
1 means closed triggers alarm
2 means open triggers alarm
3 means both closed and open triggered alarm
YY 00 means alarm not reported to control centre
10 means alarm reported to control centre 1
01 means alarm reported to control centre 2
11 means alarm reported to control centre 1 and 2
ZZZZ Selection of the alarm phone dial and alarm SMS
0 means no alarm report
1 means SMS only
2 means phone dial only
3 means SMS first, then phone dial
ZZZZ
4
th
phone number
3
rd
phone number
2
nd
phone number
1
st
phone number
NNN Relay output control
0 means no relay output control
1 means relay output triggered by alarm
NNN
3
rd
relay output (not available)
2
nd
relay output (not available)
1
st
relay output
Example 1:
PWD:1234,ALMLEVEL2:1,01,1030,100#%
Password 1234
Alarm channel 2 Once the input is closed, the alarm will be triggered
Control centre 2 will be reported by SMS
Phone number 1
Phone number 2
Phone number 3
Phone number 4
Relay output 1
Relay output 2
Relay output 3
SMS message
No report
SMS message, then phone dial
No report
Triggered
No control (not available)