terminals, refer to the following table.
Table 6: Rated cross-sections
Shaft height
Rated cross-section [mm
2
]
63 to 112 4
132 to 160 10 (r)
180 to 225 70
250 to 280 120
315 150/ 300 (depending on the model)
over 355 300
In the case of "increased safety" terminal boxes, make sure to comply with the clearances specified in EN 50019
between conductive parts having different potentials. Tighten the screws and nuts on the live parts to the specified
torque.
Table 7: Clearances
Rated voltage, U [V]
Minimum clearance [mm]
175 < U ≤ 275 5
275 < U ≤ 420 6
420 < U ≤ 550 8
550 < U ≤ 750 10
750 < U ≤ 1100 14
2200 < U ≤ 3300 36
5500 < U ≤ 6600 60
8300 < U ≤ 11000 100
Table 8: Torques and current intensities for live pins
Thread size
Torque [Nm]
Permissible continuous current
[A]
Brass Copper
M4 1.2 16 -
M5 2 25 -
M6 3 63 -
M8 6 100 -
M10 10 160 200
M12 15.5 250 315
M16 30 315 400
M20 52 400 630
Depending on the model, additional terminals for instance for temperature monitoring or space heater are located
either in the main terminal box or in additional terminal boxes; see the supplied wiring diagram.
Please note!
Take note of the rating data imprinted on the terminals.
Please note!
Keep the wiring diagram supplied in the terminal box in the enclosure with the documents belong-
ing to the drive.
Motors with unidirectional fan
Make sure that the fan's direction of rotation matches that of the motor.
Motors with separate cooling via separately powered external fans
Make sure by means of the electric control that the main motor can be operated with the motor switched-on for sepa-
rate cooling.