Introduction
Recommended Testing
3
Installation and/or maintenance of this product shall be performed by trained
professionals only.
To ensure ongoing functionality of the AC12, we recommend that you check these
interfaces every 6 months:
Short each input to its adjacent GND port and verify that LED illuminates.
Use multimeter to confirm expected impedance across relay outputs.
Closed across NC and COM
Open across NO and COM
Use multimeter to verify correct voltage is supplied at 12V AUX output, relay contact
outputs, and reader power outputs.
Check the shielding cables of the readers and other AUX wiring, if any, for proper
connection to the grounding screw(s) on the chassis.