EasyManua.ls Logo

Vertiv ALPHA 900 User Manual

Vertiv ALPHA 900
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
ALPHA 900 - 1800
Battery charger / DC Power Supply
©2017 Vertiv Co. All rights reserved | ALPHA 900 - 1800 | 6012559 | User Manual | v03 | 05.17
1 INSTALLATION
2 CONNECTION
ALPHA 1800
ALPHA 900
IMPERATIVE VERTICAL INSTALLATION
Connectors in bottom
Option Kit 6 007 983
Side mounting
Ventilation : 50mm free
space around
ALPHA UNIT
Front layout
Front layout
Side
layout
Side layout
Out : Load
External controls
4 : +Vcc
5 : 0V
6 : U setting (switch 2 set to external setting)
7 : IB setting (switch 3 set to external setting)
8 - 9 : ON / OFF static stop (open = stop)
10-11 : boost
Fault report
1-2 : NO
2-3 : NC (closed at fault)
*
: Earth ()
Mains
(male IEC type)
Fault
fault
Stop
Boost
DJS curve C :
6A Alpha 900
16A Alpha 1800
220/240Vac
50/60Hz
Terminal +/- wire
Mini 0.75mm²
900 MAXI 10mm²
1800 MAXI 16mm²
Terminal 1 to 11
0,8mm² mini
2,5mm² maxi
U & IB = option Kit
External Potentiometer
Réf. : 6 002 928
*
To more information, to see
“6007539 Alpha 900 user’s manual”
or “6008595 Alpha 1800 user’s
manual
Question and Answer IconNeed help?

Do you have a question about the Vertiv ALPHA 900 and is the answer not in the manual?

Vertiv ALPHA 900 Specifications

General IconGeneral
BrandVertiv
ModelALPHA 900
CategoryBattery Charger
LanguageEnglish

Summary

INSTALLATION

Vertical Installation Requirement

Units must be installed vertically with connectors at the bottom for proper operation and safety.

CONNECTION

Mains and Battery Connections

Details on AC input, DC output, battery, and load terminal connections, including wire specifications.

Fault Reporting and External Controls

Information on interpreting fault reports and connecting external control signals for unit operation.

CONFIGURATION

Mode Selector and Voltage/Current Settings

Explains the mode selector's functions for charger or power supply modes and output voltage/current settings.

QUARTZ Supervisor Integration

Details on configuring the ALPHA unit to operate under the control of a QUARTZ supervisor system.

I/O PCB Terminal Functions

Describes the functions of terminals on the I/O PCB, including remote control and status reporting.