UPGRADEABLE PDU
Quick Installation Guide
VM1158/590-2142-501B 1
Installing the unit
a. Using appropriate hardware,
mount unit to rack.
b. Plug the PDU into appropriately
rated and protected branch
circuit receptacles.
c. Plug in devices to be powered
by the PDU.
d. Power on devices that are
powered by the PDU.
Sequential power up is
recommended to avoid high
in-rush current.
Configuring IP addressable
units
The PDU is equipped with and
RJ45 Ethernet port for attachment
to an existing network. The PDU is
configured with the following
default network settings to allow
unit configuration:
IP address:
192.168.123.123
Subnet Mask:
255.255.255.0
Gateway:
192.168.123.1
The local PC network connection
must be configured as follows:
IP Address:
192.168.123.x (where x is 2-253,
except 123)
Subnet Mask:
255.255.255.0
Gateway:
<leave blank>
Environmental
TEMPERATURE
Operating 10°C (50°F) min 60°C (140°F) max
Storage -25°C (-13°F) min 65°C (149°F) max
HUMIDITY
Operating 5% min 95% max (non-condensing)
Storage 5% min 95% max (non-condensing)
ELE VAT IO N
Operating 0 m (0 ft) min 3050m (10,000 ft) max
Storage 0 m (0 ft) min 15240 m (50,000 ft) max

Other manuals for Vertiv Geist

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Geist and is the answer not in the manual?

Vertiv Geist Specifications

General IconGeneral
ConnectivityEthernet, Serial
Product TypePower Distribution Unit (PDU)
BrandVertiv
Input Frequency50/60 Hz
Form FactorRackmount
MountingVertical, Horizontal
CertificationsUL, CE