Liebert® CRV CRC30 and CRC60
User Manual (Original Instructions)
30 kW and 60 kW, 50 Hz, Chilled Water Cooling System

Table of Contents

Questions and Answers

  • B
    Brian CarsonAug 14, 2025
    Why is the rack temperature too high in my Vertiv Water System?
    • M
      Matthew CampbellAug 14, 2025
      High rack temperatures in your Vertiv Water System can stem from several causes. Check for dirty filters and replace them if necessary. Ensure that remote temperature sensors are correctly positioned. Verify the cooling water temperature, as an inlet water temperature that is too high can also cause this issue. Additionally, cold air short-cycling or insufficient room cooling capacity can contribute to the problem, so verify unit positioning/room configuration and consider reducing the rack heat load or adding cooling units.
  • W
    William SanchezAug 17, 2025
    What to do if there's water on the floor around my Vertiv Liebert CRV CRC60 Water System unit?
    • D
      Dr. Mary King MDAug 18, 2025
      If you find water on the floor around your Vertiv Water System unit, it could be due to several reasons. First, check if the unit is properly leveled and adjust the leveling feet if needed. Also, inspect the unit condensate drain pipe for any clogs and remove any obstructions. A leak in the water circuit could also be the cause; locate and repair any leaks. Finally, examine the piping insulation for any breaks or damage and restore the insulation integrity.
  • R
    Ronald JenningsAug 21, 2025
    What to do if my Vertiv Liebert CRV CRC60 local display is not operational and the unit does not operate?
    • E
      Erin ChambersAug 21, 2025
      If the local display of your Vertiv Water System is not working and the unit isn't operating, start by checking the unit's electrical supply and restore it if it's off. Also, ensure that the unit's main circuit breaker is switched on.
  • D
    Darius GlennAug 25, 2025
    Why is the air delivery temperature unsteady in my Vertiv Liebert CRV CRC60 Water System?
    • J
      James CruzAug 25, 2025
      An unsteady air delivery temperature in your Vertiv Water System can be caused by a few things. Make sure the remote temperature sensors are correctly positioned. An unbalanced heat load distribution can also lead to this issue, so try to redistribute the rack heat load.
  • J
    joseph58Aug 27, 2025
    How to fix low supply temperature alarm or room over-cooling in Vertiv Liebert CRV CRC60 Water System?
    • D
      Dr. Brittany BarryAug 27, 2025
      To address a low supply temperature alarm or room over-cooling with your Vertiv Water System, consider these steps. If applicable, place a unit into standby. Ensure proper airflow by installing blanking panels in open areas of racks. Check the cooling water temperature, as an inlet water temperature that is too low can also cause this issue.
  • S
    Steven CareyAug 31, 2025
    What causes water drops carried by airflow in Vertiv Water System?
    • C
      Carol BanksAug 31, 2025
      Water droplets being carried by the airflow in your Vertiv Water System could indicate that the room humidity is over the acceptable limit. Check the room conditions to ensure they are within the recommended range.
  • L
    Lindsey AdamsSep 3, 2025
    What to do if the Vertiv Liebert CRV CRC60 Water System local display is not operational but the unit operates?
    • T
      Terry JacksonSep 3, 2025
      If your Vertiv Water System unit operates but the local display is not working, check if the local display cable is disconnected and connect it. If the cable is damaged, replace it.
  • S
    Samuel RiosSep 6, 2025
    What causes low room humidity in Vertiv Water System?
    • C
      charlesrogersSep 7, 2025
      Low room humidity in your Vertiv Water System setup can stem from a humidifier problem. Check the fault LED on the humidifier PCB enclosure. It can also be caused by the room humidity exceeding the humidity control band. Verify set points and confirm the room is properly sealed.
  • J
    Jennifer KingSep 10, 2025
    Why is there no heating effect when the contractor is engaged in my Vertiv Liebert CRV CRC60?
    • S
      Stacy SparksSep 10, 2025
      If the contractor is engaged but there's no heating effect in your Vertiv Water System, check that the voltage of the contractor is within the normal range. If the voltage is correct, the heater may be damaged and need replacement.

Summary

Important Safety Instructions

Pre-installation Preparation

Moving the Packaged Unit

Details safe procedures for moving the packaged unit with a forklift.

Removing the Unit from the Pallet

Explains how to safely remove the unit from the shipping pallet.

Installing in Enclosure Row

Leveling the Unit

Details the procedure for leveling the unit correctly.

Combining the Unit with Adjacent Cabinets

Explains how to bay units together using brackets.

Piping Connections

Connecting Water Inlet and Outlet Pipes

Provides instructions for connecting water inlet/outlet pipes.

Releasing Pre-charged Nitrogen

Describes how to release pre-charged nitrogen from the unit.

Top Connection

Details connecting pipes through the top panel.

Bottom Connection

Details connecting pipes through the bottom panel.

Connecting Condensate Drainage Pipes

Explains how to connect condensate drainage pipes.

Top Connection

Describes connecting condensate drainage via the top.

Bottom Connection

Describes connecting condensate drainage via the bottom.

Electrical Connections

Connecting Power Supply Cable

Instructions for connecting the main power supply cable.

Connecting Power Supply Cable for CRC30

Specific steps for CRC30 power cable connection.

Connecting Power Supply Cable for CRC60

Specific steps for CRC60 power cable connection.

Connecting Communications Cables

Details for connecting various communication cables.

Start-up

Commissioning

Procedures for unit commissioning by authorized professionals.

Start-up

Steps involved in starting up the unit.

First Start-up (or After Long Standstill)

Detailed steps for initial or post-standstill start-up.

Maintenance

Maintenance Schedule

Provides a schedule for monthly, quarterly, biannual, and annual checks.

Troubleshooting

Lists common problems, causes, and corrective actions.

Vertiv Liebert CRV CRC60 Specifications

General IconGeneral
BrandVertiv
ModelLiebert CRV CRC60
CategoryWater System
LanguageEnglish