2. In COV field, toggle any data set point you want to have poll GW2 whenever Device has change in present value up to a
maximum of 20 per device.
NOTE: The GW2 polls a point at a regular interval unless COV is checked. When COV is checked, the Room Controller sends
(pushes) updated values back to GW2 whenever they change. Also, adding COV on points that change frequently creates more
traffic on the network.