HAZARD IDENTIFICATION
Definitions for identifying the various hazard levels are provided below. When you see this symbol, be alert to the possibility of
personal injury. Carefully read and fully u nderstand the message that follows.
DANGER
The use of the word “DANGER” identifies an immediate
hazard with a likelihood of death or serious personal injury if
instructions are not followed.
WARNING
The use of the word “WARNING” identifies the presence of
hazards or unsafe practices that could result in death or serious
personal injury if instructions are not followed.
CAUTION
The use of the word “CAUTION” identifies possible hazards or
unsafe practices that could result in personal injury and product
or property damage if instructions are not followed.
NOTICE
The use of the word “NOTICE” identifies special instructions
that are important but not related to hazards.
DEFINITIONS FOR "SHOULD" AND "SHALL" REFERENCES USED THROUGHOUT THIS MANUAL
References to "should" within this manual indicate areas of importance that are to be taken under consideration, but are not a requirement.
References to "shall" within this manual indicate areas of critical importance that are a requirement.
SYSTEM DESIGN FOR TOTAL FLOODING APPLICATIONS –
HYBRID MEDIA QUANTITY, HYBRID EMITTER SELECTION, AND SYSTEM PERFORMANCE
Acceptable applications can be determined by referencing the FM Listing and FM Loss Prevention Data Sheets
WARNING
The Victaulic Vortex
system SHALL NOT be used in areas that contain the following materials, unless approved by the AHJ:
Chemicals or mixtures of chemicals, such as cellulose nitrate and gun powder, that are capable of rapid oxidation in the absence of air
Reactive metals, such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium, and plutonium
Metal hydrides
Chemicals, such as certain organic peroxides or hydrazine, that are capable of undergoing autothermal decomposition
Failure to follow these instructions could result in death or serious personal injury and property damage.
Hybrid
Emitter
Acceptable Operating
Pressure Range
Required Water Flow
Control Cartridge
Recommended
Discharge Time
¼-inch
PVDF
38 – 42 psi
2.6 – 2.9 Bar
0.26 GPM
1 LPM
2 Minute Minimum
VDM-VORTEX.04_2 REV_A