23
Fault Cause Measures
Whining noises Incorrect CO
2
set-
tings; insufficient or
excessive air
Adjust burner according to the informa-
tion in the Vitocrossal service instruc-
tions.
CO
2
content too
low
Incorrect setting Check that the burner has been set for
the correct gas type, change gas restric-
tor if required (see Vitocrossal service in-
structions).
Adjust burner according to the informa-
tion in the Vitocrossal service instruc-
tions.
CO is formed or
burner is very sooty
Insufficient or too
much air
Correct settings. Check ventilation in in-
stallation room.
Insufficient draught
in flue system
Check flue system.
Excessive flue gas
temperature
Excessive gas
throughput
Adjust the gas throughput according to
the rated boiler heating output (see con-
nection values in the Vitocrossal service
instructions).
Check condition of secondary heating
surfaces of the boiler and clean if re-
quired.
Diagnosis
Diagnosis
(cont.)
5782 991 GB
Service