Required parameter settings
ID: 4605357_1304_04
Parameter Value Function
7000 6 With heating circuit A1/HC1, M2/HC2, DHW cylinder
7B00 1 Enable external heat source, oil/gas boiler
7B0D 1 Enable external heat source for DHW heating
5030 according to type plate Rated heating output, heat pump stage 1
5130 according to type plate Rated heating output, heat pump stage 2
ID: 4605357_1304_04
Vitotronic 200, type KO1B / KO2B / KW6B
Parameter Value Function
General 3A : 3 Blocking of the external heat source
General 3b : 2 External demand
General 9b : 70 Set value for external demand
Hydraulic installation scheme ID: 4605357_1304_04