6.2 Vitocal 200-A with one heating/cooling circuit without mixer, with active cooling func-
tion and DHW heating
ID: 4605547_1304_02
Application range
Detached houses with uniform user patterns, underfloor heating and
cooling demand. Size the DHW cylinder in accordance with current
standards and requirements.
Main components
■ Vitocal 200-A with Vitotronic 200, type WO1C
■ 1 heating/cooling circuit without mixer
■ DHW cylinder
Requirements
The minimum flow rate of the heat pump must be safeguarded by sec-
ondary pump
6
and overflow valve
oE
. This valve must be installed
at the furthest point of the underfloor heating distributor and be
hydraulically balanced.
Central heating by heat pump
Heat pump
1
supplies heating circuit
oP
with heat via secondary
pump
6
. Heat pump control unit
2
regulates the heating water flow
temperature and thereby the heating circuit.
Heat pump
1
starts if the actual temperature captured by flow tem-
perature sensor
7
in heat pump
1
is lower than the set temperature
selected at control unit
2
.
The flow rate within the heating circuit is regulated by opening and
closing the valves at the underfloor heating system distributor.
Heat pump
1
and secondary pump
6
are switched off once the
actual flow temperature exceeds the temperature set at control unit
2
.
DHW heating
In the delivered condition, DHW heating by heat pump
1
is given
priority over the heating circuits and takes place from 00:00 to
24:00 h.
The heat demand is issued via cylinder temperature sensor
eQ
and
control unit
2
, which controls 3-way diverter valve
5
in conjunction
with secondary pump
6
. The control unit raises the flow temperature
to the value required for DHW heating.
The cylinder temperature can be raised to 60 °C via instantaneous
heating water heater
4
.
Active cooling function
The active cooling function is enabled if the value for the cooling limit
temperature that can be adjusted at control unit
2
is exceeded at
outside temperature sensor
3
.
The heat pump supplies heating circuit
oP
with cooled heating
water.
Control unit
2
regulates the flow temperature and thereby the cooling
function of the heating circuit in line with the selected cooling param-
eters.
The set flow temperature of the cooling circuit is regulated in accord-
ance with the cooling demand.
Possible condensate that may form as a result of changing ambient
conditions is captured by contact humidistat
iE
and central cooling is
switched off if necessary.
Note
All lines where the coolant temperature can fall below the dew point
should be insulated so that they are vapour diffusion-proof.
In cooling mode, safeguard the minimum flow rate in the secondary
circuit.
To do so, use suitable valves on the heating circuit distributor. See the
Vitoset pricelist.
Required parameter settings
ID: 4605547_1304_02
Vitotronic 200, type WO1C
Parameter Value Function
7000 2 With heating circuit A1/HC1, DHW cylinder
7100 3 Enable active cooling function
7101 1 Cooling via heating circuit A1/HC1
7103 180 Min. flow temperature, cooling
6014 1 Enable immersion heater for DHW reheating
2003 1 Vitotrol 200A remote control activated for heating circuit A1/HC1