4.6 Vitocal 300-G/350-G, one heating circuit without mixer, one heating circuit with mixer,
DHW heating and heating water buffer cylinder
ID: 4605354_1304_03
Application range
Detached house and apartment building with two heating circuits with
different design layouts. Size DHW cylinder
eP
in accordance with
current standards and requirements.
Main components
Vitocal 300-G/350-G, type BW or BWC, up to 18.7 KW
Vitotronic 200, type WO1B
Heating circuit distributor with one heating circuit without mixer and
one heating circuit with mixer
DHW cylinder
Heating water buffer cylinder
Heating water buffer cylinder
The minimum flow rate of heat pump
1
is safeguarded via heating
water buffer cylinder
zP
and secondary pump
6
. It is possible to use
differential pressure-dependent heating circuit pumps
uZ
and
oZ
.
Central heating by heat pump
Heat pump
1
, primary pump
5
and secondary pump
6
start when
the actual temperature captured by cylinder temperature sensor
zQ
of
heating water buffer cylinder
zP
falls below the set temperature selec-
ted at control unit
2
.
Control unit 2 regulates the heating water flow temperature. With
type BW heat pumps, secondary pump
6
delivers heating water sub-
ject to demand to heating water buffer cylinder
zP
, or via circulation
pump for cylinder heating
7
to DHW cylinder
eP
.
With type BWC heat pumps, integral secondary pump
6
or the cir-
culation pump for cylinder heating delivers heating water
7
either to
heating water buffer cylinder
zP
or to DHW cylinder
eP
.
To balance the difference in energy between the primary and secon-
dary circuits, operate heating water buffer cylinder
zP
in parallel to the
heating circuits. Any heat not absorbed by the heating circuits is stored
in heating water buffer cylinder
zP
. In addition, heat pump
1
achieves
longer runtimes, and the heating circuits are supplied with heat from
heating water buffer cylinder
zP
during power-OFF periods.
DHW heating by heat pump
In the delivered condition, DHW heating by heat pump
1
is given
priority over the heating circuits and takes precedence at night.
With BW type heat pumps, the heat demand is issued via cylinder
temperature sensor
eW
and control unit
2
, which controls circulation
pump for cylinder heating
7
. Heat pump
1
raises the flow temper-
ature to the value required for DHW heating.
With type BWC, the demand is issued via cylinder temperature sensor
eW
and control unit
2
, which controls integral circulation pump for
cylinder heating
7
.
The flow temperature can be raised above 60 °C with instantaneous
heating water heater
4
.
Required parameter settings
ID: 4605354_1304_03
Parameter Value Function
7000 6 With heating circuit A1/HC1, M2/HC2, DHW cylinder
Vitocal 300-G/350-G
(cont.)
100
VIESMANN
System examples