72
1C Signal B4 at plug 41
Display Value Explanations
Burner start delay from the presence of the start sig-
nal at T2 in plug
fA
until burner ignition
Note
Factory settings, according to coding card
... s 1C:1 to
1C:199
1F Flue gas temperature sensor
!
Display Value Explanations
Flue gas temperature is not monitored for
burner service display
1F:0
... °C limit for service 1F:1 to
1F:250
21 Interval in burner hours until the next service
!
Display Value Explanations
Not active 21:0
... h 21:1 to
21:100
Interval adjustable from 100 to 10,000 h.
1 step ≙ 100 h
23 Interval until the next service
!
Display Value Explanations
Not active 23:0
... Months 23:1 to
23:24
The number of months before the next service is ad-
justable from 1 to 24
24 Service status
!
Display Value Explanations
No service due 24:0
Service due and indication on display 24:1
26 Burner fuel consumption (stage 1)
Display Value Explanations
0 26:0 Never adjust
... 26:0 to
26:99
Parameter
Boiler (cont.)
5863679
Parameter