D-303404 GSD-442 PG2 Installation Instructions 3
APPENDICES
Appendix A - Specifications
CO DETECTION
Detection Principle
Electrochemical cell
Detector Active Life
5 years
Selectable Sensitivity
DIP switch in EN mode:
No warning at 30 ppm for 120 minutes, 50 ppm for 60 minutes, 100 ppm for 10 minutes.
Warning at 50 ppm between 60-90 minutes, 100 ppm for 10-40 minutes, 150 ppm within 3 minutes
DIP switch in UL mode:
No warning at 30 ppm for 30 days,, 70 ppm for 60 minutes, 150 ppm for 10 minutes, 400 ppm for 4
minutes.
Warnin
g
at 70 ppm between 60-240 minutes, 150 ppm for 10-50 minutes, 400 ppm between 4-15minutes
Audible Alarm Volume
>85db at a distance of 3m (10 ft.)
WIRELESS
Frequency Band (MHz)
Europe and rest of world: 433-434, 868-869 USA: 912-919
Communication Protocol PowerG
Supervision
Automatic signaling at 60-minute intervals (912-919 MHz version), 15-minute intervals (433-434, 868-869
versions) or according to the local standards.
Transmitted Messages CO gas alarm, low battery, tampe
r
, trouble message as a result of sensor end of life or sensor trouble,
supervision.
Tamper Alerts Tamper message is transmitted to the PowerMaster control panel when the detector is removed from its
bracket.
ELECTRICAL DAT
A
Power Source
9 Volt Lithium battery (Ultra Life #U9VL, U9VL-J), or Alkaline battery, Energizer #522.
Current Drain
55 μA average current consumption
Battery Supervision Automatic transmission of battery status data as part of any transmitted message.
Batter
y
Life Expectanc
y
At least 1
y
ear
(
for t
y
pical use
)
Low Battery Threshold 7.8 V
Audible and Visual
Indications
Condition
Visual Indication (LEDs) Audio
Indication
Red Yellow Green
Alarm 4 flashes (*) - - 4 beeps (*)
End of Life / Fault - 3 flashes every
60 sec.
- one beep every 60
sec.
Battery OK - - Flashes once
every minute
-
Low battery - 1 flash every 60
sec.
- One beep every 60
sec.
MUTE button is
pressed (to silent the
alarm for 6 minutes)
4 flashes (*) - - OFF for 6 minutes (**)
TEST button is
pressed
1 flash (the 1st
LED)
1 flash (the 2nd
LED)
Flashes (the 3rd
LED) If CO circuit
test and battery
are OK - lights
during 2 sec.
1 beep
* Every 5 seconds during the first 4 minutes, every 60 seconds after the first 4 minutes.
** Every 6 minutes the detector restarts the alarm if the CO level remains high.
Note: Long period of low battery condition may cause improper function. In case of End-of-Life/Fault
indication, replace the battery and check if the End-of-Life/Fault indication still exists. If it still exists, stop
usin
g
the detector.
PHYSICAL DAT
A
Operating Temperatures 0°C to 40°C (32°F to 104°F)
Relative Humidit
y
10% to 93% 2% RH
Dimensions 127 mm (5 in.) x 40 mm (1-9/16 in.)
Weight (with battery)
180 g (6.35 oz)
Appendix B - CO Detector Installation Overview
B-1. Selecting Installation Location
Selecting a suitable location is critical for the CO detector. The Consumer Product Safety Commission (CPSC) recommends to use at
least one CO detector per household, located near as possible to sleeping areas of the home, because the human body is most
vulnerable to the CO gas effect during sleeping hours.
For added protection, install additional CO detectors in every separate bedroom and on every level of your home. If your bedroom
hallway is longer than 14 meters (40 feet), install a CO detector at BOTH ends of the hallway. Install an additional detector 6 meters (20
feet) away from the furnace or fuel burning heat source.