Table with parameters
Parameter code Description Value range Factory setting Unit
Parameter Menu CP
diF Temperature step width "1 - 30" 2 °C/°F
HSE Set maximum temperature "LSE - 99" 99 °C/°F
LSE Set minimum temperature "-55 - HSE" -55 °C/°F
HC Control mode (H = heat; C = cool) "H/C" H /
If the temperature sensor fails, the compressor is shifted to the cycle
mode:
Ont On t: Runtime for the switched-on phase On t: Runtime for the switched-on phase of the cycle. 0 Minutes
OF t: Runtime for the switched-off phase of the cycle.
Ont=0;OFt=1: Compressor remains off.
OFt Ont=1;OFt=0: Compressor is permanently on. "0-250" 1 Minutes
Ont≠0;Ont≠0: Compressor runs in the cycle
with the times for the switched-on and -off phases as described above.
dOn Delay time until the compressor starts "0-250" 0 Seconds
dOF Time interval between the "0-250" 0 Minutes
dbi The time interval between two consecutive comp. start processes "0-250" 0 Minutes
OdO Time delay of the output after the device switches on "0-250" 0 Minutes
Parameter Menu diS
LOC Button lock (n = buttons not blocked, y = buttons locked)
It is possible to program the parameters further
"n/Y" n /
PA1 User password "0-250" 0 /
ndt Display the decimal point: y = yes; n = no "n/Y" n /
CA1 Calibrate temperature "-12-12" 0 °C/°F
dro Temperature unit (0 = °C, 1 = °F) "0/1" 1 /
Parameter Menu CnF
H00 Selection of the sensor type (0 = PTC, 1 = NTC) "0/1" 1 /
rEL Device version "/" / /
tAb Parameter overview "/" / /
The target value [SEt] should always be between the parameters [LSE] (lowest target value to be set) and [HSE] (highest target value to be set). For example, if [HSE] is set to 10, the
target value cannot be set higher.