If need programmable relay output time-delay, the delay time is set by F4 code.
●When the FJ is set as 5-9(or 15-19), the programmable operation way is time
sequence output, As the following form:
● The way of programmable state output is used to show the working state of soft
state, and under this way, the F4 code is un-useful; The ex-factory value of FJ
code is "7"showing the ready state of soft starter and at this time the motor can be
started up; when the programmable output is in fault state, the faults m>>mean
the fault of motor, such as fault of Err05, Err06, Err12, Err15,and they are different
form the faults come from the terminals⑤⑥ output.
● When FJ>9,the reset state of programmable output is normal closed ,that is”
inverse phase output"
5.4 The function of Re-start
When the FE item is not set as "0", the Automatic Re-start function is in use. This
function is affective only the External Control connection is 2-wire way and is not
controlled by the FD item (External Control allowed). When it is 2-wire way you
can:
● Having got electricity and delay time for 60 seconds, the soft starter will Re-start