Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 4 INITIAL START-UP
OMM-0143_A GF-216 9/6/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 61 of 170
Combustion Calibration Instructions
TABLE 4.3-1: Gas Pressure Downstream of SSOV
INN 600N
1.9 ± 0.2” W.C.
473 ± 50 Pa
INN 800N
1.7 ± 0.2” W.C.
423 ± 50 Pa
INN 1060N
1.9 ± 0.2” W.C.
473 ± 50 Pa
INN 1350N
1.9 ± 0.2” W.C.
473 ± 50 Pa
Figure 4.3-4. SSOV Gas Pressure Adjustment Screw Location
13. With the valve position still at 100%, and the combustion analyzer probe in the exhaust
manifold probe opening (see Section 4.2.3):
a. Allow enough time for the combustion analyzer reading to stabilize.
b. Note the combustion analyzer’s oxygen (O
2
) reading.
c. If it doesn’t match the value in the O2 Target cell, adjust the Blower Voltage using
either the + or controls, or press on the field and type the value directly, until the O
2
value matches the O2 Target.
d. Once it matches the O2 Target, press the O2 Reading cell and enter the value.
14. Enter the downstream manometer’s gas pressure reading in the Downstream Gas
Pressure field. Note, this field appears only when Valve Position % = 100%.
15. Enter the Flame Strength, NOx and CO readings from the Combustion Analyzer and
multi-meter in the Reading cells.
16. Enter the same values, plus the O
2
value, on the Combustion Calibration Data Sheet
provided with the unit.
17. Compare the NOx and carbon monoxide (CO) values in the Reading and Target columns.
If NOx readings exceed the target values in Table 4.3-2, below, repeat Step 13c to
increase the O
2
level up to 1% higher. You must then record the increased O
2
value on the
Combustion Calibration sheet (repeat Step 16).
NOTE:
These instructions assume that the inlet air temperature is between 50°F and 100°F
(10°C 37.8°C).
18. Lower the Valve Position to the 80% calibration point using either the (Left) arrow key or
the Fine Valve Position (Minus) key, then repeat step 13 and 17 at that valve position.
The O
2
, NOx and CO should stay within the ranges shown in these tables. If they are not in
the ranges shown, check the following:
BRASS HEX HEAD CAP
(Remove cap to access gas
pressure adjustment screw)