Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 5 – SAFETY DEVICE TESTING
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 72 of 170
Flame Fault Tests Instructions
11. Open the valve closed in step 8.
12. Press the CLEAR button. The unit should restart and fire.
Figure 5.7: Manual Gas Shut-Off Valve Location (INN600N-800N Gas Train Shown)
5.8 AIR FLOW FAULT TESTS
These tests check the operation of the Blower Proof switch and Blocked Inlet switch shown in
Figure 5.8-2.
Air Flow Fault Tests Instructions
1. Put the unit in Manual Mode by going to the Main Menu → Diagnostics → Manual Run
and setting the Manual Mode toggle to Enabled, then set the valve position to 25%.
2. Disable the blower output drive voltage as follows:
(a) Go to: Main Menu → Diagnostics → Analog Outputs and Relays → Analog
Outputs.
(b) Press the Manual button, then press the Zero button. The Blower slider now read
0.00.