16
en
ITXPlus
• Operation
General
The ITXPlus is a DIN rail device that converts signals from commonly
us
ed industrial signal sources and provides a fully isolated 4-20 mA
signal that varies in proportion to the input signal.
Loop powered operation
Loop powered transmitters use the drop in voltage across the outputs
to g
enerate power for the electronics. The ITXPlus requires a 10-40 V
drop to operate correctly. Using a power supply that provides this
voltage drop will comply with the instrument’s UL/CSA listing.